Plan Review Notes For Permit 01041098 |
Permit Number |
01041098 |
|
Review Stop |
FS |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-04-24 00:00:00 | 1) A SPARE HEAD BOX IS TO BE PROVIDED. | | 2) FIRE DEPARTMENT CONNECTION IS TO BE | | NO MORE THAN 150 FEET FROM A FIRE | | HYDRANT. | | 3) PORCH C12 AND C13 ARE TO BE | | PROTECTED. | | 4) EXISTING BACKFLOW DEVICE IS TO BE | | CHAINED AND LOCKED WITH TAMPER SWITCHES | | SINCE NO INDICATING VALVES ARE PRESENT | | AT THE BUILDING. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|