2001-08-20 00:00:001) IT APPEARS THAT AN EXIT DOOR (C)
 DISCHARGES INTO AN AREA USED FOR A
 DUMPSTER ENCLOSURE WITH GATES. THIS
 ARRANGEMENT IS NOT PERMITTED. THIS EXIT
 IS REQUIRED SINCE THE OTHER TWO EXITS
 DO NOT MEET THE 1/2 THE LENGTH OF THE
 AREA OR ROOM SERVED.
 2) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. PLEASE SUBMIT FIRE
 SPRINKLER DRAWINGS AND HYDRAULIC
 CALCULATIONS. THE FIRE DEPARTMENT
 CONNECTION IS TO BE WITHIN 150 FEET OF
 A FIRE HYDRANT.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE SPRINKLER TRANSMITTER
 PLANNED FOR USE. THE FIRE SPRINKLER
 SYSTEM IS REQUIRED TO BE MONITORED BY
 A LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910