2002-09-26 00:00:00DENIED:
  
 PLEASE CLARIFY OUTSIDE AIR
 INTERPRETATION FOR "INTERMITTENT
 OCCUPANCY" 15 CFM PER PERSON.
  
 PLEASE INDICATE HOW MANY PEOPLE WILL BE
 WORKING IN EACH SPACE.THIS IS NOT
 CONSIDERED "INTERMITTENT OCCUPANCY".
 "INTERMITTENT OCCUPANCY" CAN BE
 CALCULATED FOR THE MAXIMUM CAPACITY FOR
 THE CUSTOMERS ONLY, IN NO CASE SHALL
 THE CFM BE LESS THAN 30 CFM PER PERSON
 AS REQUIRED BY ASHRAE 62-89 SEC 6.1.3.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.