Plan Review Notes
Plan Review Notes For Permit 01041075
Permit Number 01041075
Review Stop P
Sequence Number 4
Notes
Date Text
2001-12-10 00:00:00PLUMBING PLAN REVIEW,DENIED. PREVIOUS
 COMMENTS DATED 10-28-01 NOT APPROVED.
 (1) GREASE TRAPS TO BE PIPED PARALLEL.
 (2) WATER HAMMER ARESSTORS TO BE INSTAL-
 LED AS PER MFG. NOT AT HIGH POINT.
 (3) PROVIDECUT SHTS FOR 2# REGULATORS.
 SHOW MANUAL SOV & UNION UP STREAM OF
 REGULATOR.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS 561-659 8096X8233