2001-10-28 00:00:00 | PLUMBING PLAN REVIEW, DENIED | | (1) SHT P-3-4GREASE TRAP REFERENCE, | | GREASE TANKS TO BE PIPED PARALLEL NOT | | IN SERIES. | | (2) SHT P-2 WATER PIPING ISOMETRIC SHOW | | A REERENCE FOR WATER HAMMER ARRESTORS, | | INSTALLED PER.MFG FOR PLACEMENT AND | | LOCATION,SEC 607.8, PDI-WH201, ASSE 1010 | | (3) SHT P-2 GAS PIPING ISOMETRIC L-P GAS | | CODE REFERENCE FOR L-P GAS IS NFPA-54-99 | | LIQUIDFIED PETROLEM, TAB 12.1 TANK TO | | METER, TAB 12.3 SECOND STAGE REGULATOR | | TO APPLIANCE. | | TOTAL DEVELOPED LGTH SHALL BE FROM L-P | | TANK TO METER, METER TO THE FARTHEST | | APPLIANCE. | | PIPING AS SHOWN IS OVER SIZED. | | SPECIFICATIONS CALL FOR ALL BLK STEEL | | PIPING TO BE WELDED, REGARDLESS OF SIZE? | | END OF COMMENTS PAUL SCHMITZ | | QUESTIONS 5610659-8096X8233 |
|