2001-10-28 00:00:00PLUMBING PLAN REVIEW, DENIED
 (1) SHT P-3-4GREASE TRAP REFERENCE,
 GREASE TANKS TO BE PIPED PARALLEL NOT
 IN SERIES.
 (2) SHT P-2 WATER PIPING ISOMETRIC SHOW
 A REERENCE FOR WATER HAMMER ARRESTORS,
 INSTALLED PER.MFG FOR PLACEMENT AND
 LOCATION,SEC 607.8, PDI-WH201, ASSE 1010
 (3) SHT P-2 GAS PIPING ISOMETRIC L-P GAS
 CODE REFERENCE FOR L-P GAS IS NFPA-54-99
 LIQUIDFIED PETROLEM, TAB 12.1 TANK TO
 METER, TAB 12.3 SECOND STAGE REGULATOR
 TO APPLIANCE.
 TOTAL DEVELOPED LGTH SHALL BE FROM L-P
 TANK TO METER, METER TO THE FARTHEST
 APPLIANCE.
 PIPING AS SHOWN IS OVER SIZED.
 SPECIFICATIONS CALL FOR ALL BLK STEEL
 PIPING TO BE WELDED, REGARDLESS OF SIZE?
 END OF COMMENTS PAUL SCHMITZ