2001-08-02 00:00:00SHEET S1 OF THE PUBLIX PLANS DESIGN
 CRITERIA CALLS OUT CONFLICTING
 INFORMATION FOR THE WIND.SEE SBC
 1606.1.2.1 RE: MIXING OF WINDLOADS.
 THE ENTIRE BUILDING, INCLUDING THE
 RETAIL WINGS, MUST BE DESIGNED TO ONE
 STANDARD.EITHER ASCE 7-95 OR SBC
 1606.2.WEST PALM BEACH IS IN THE 140
 MPH VELOCITY ZONE FOR ASCE 7-95 AND 110
 MPH FOR SBC 1606.2. NOT THE 100 MPH
 DECLARED.
  
 PLEASE INCLUDE CALCULATIONS
 DEMONSTRATING COMPLIANCE WITH ONE OF
 THE ABOVE.ALSO WHICH IS THE DESIRED
 SOIL BEARING PRESSURE,2000 PSF OR 2500
 PSF?
  
 THE FP1 HAS A STATEMENT THAT SAYS SEE
 THE ARCHITECTURAL PLANS FOR THE CANOPY
 SPRINKLER DESIGN.THE ARCHITECTURAL
 PLANS DO NOT SHOW ANY FIRE SPRINKLER
 DESIGN.
  
 NFPA 13 SS 4-5.7.1 REQUIRES SPRINKLERS
 FOR THIS APPLICATION AND CHP.
 61G15-32.003 COMMON REQUIREMENTS TO ALL
 FIRE PROTECTION ENGINEERING DOCUMENTS
 FBPE,SET OUT SPECIFIC INFORMATION FOR
 DOCUMENT SUBMITTAL.PLEASE REVISE AS
 NECESSARY.
  
 PLEASE INDICATE THE PORTIONS OF THE
 BILDING THAT WILL HAVE HURRICANE
 SHUTTERS AND WHICH WILL HAVE IMPACT
 RESISTANT GLASS?
  
 SEE THE PREVIOUS CHECKLISTS REGARDING
 IMPACT FEES AND A RESIDENT INSPECTOR.