2001-08-15 00:00:00********************DENIED**************
  
  
 PLAN SHEET A-6, FLUE PIPE SHALL BE NO
 LESS THAN 10' FROM ANY FRESH AIR INTAKE.
 (1997 SGC 608.3.1)
  
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN
 COOLERS/FREEZERS.PLEASE PROVIDE PLANS
 AND ALL MANUFACTURER SUBMITTAL DATA AT
 THE TIME OF PERMIT APPLICATION.
  
 PROVIDE INFORMATION ON THE MECHANICAL
 CENTERS ON THE ROOF, SHOW COMPLIANCE
 WITH CHAPTER 11 OF THE 1997 SMC.
  
  
 NOTE:CONDENSERS INDICATED ON PLAN
 SHEET A-6, CONDENSER STANDS SHALL
 BE A MINIMUM OF 18" BETWEEN ROOF
 SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL. (AMENDED 1997 SMC
 304.2.5)