Notes |
Date |
Text |
2001-08-15 00:00:00 | ********************DENIED************** | | | | | | PLAN SHEET A-6, FLUE PIPE SHALL BE NO | | LESS THAN 10' FROM ANY FRESH AIR INTAKE. | | (1997 SGC 608.3.1) | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | FIRE SUPRESSION AND WALK-IN | | COOLERS/FREEZERS.PLEASE PROVIDE PLANS | | AND ALL MANUFACTURER SUBMITTAL DATA AT | | THE TIME OF PERMIT APPLICATION. | | | | PROVIDE INFORMATION ON THE MECHANICAL | | CENTERS ON THE ROOF, SHOW COMPLIANCE | | WITH CHAPTER 11 OF THE 1997 SMC. | | | | | | NOTE:CONDENSERS INDICATED ON PLAN | | SHEET A-6, CONDENSER STANDS SHALL | | BE A MINIMUM OF 18" BETWEEN ROOF | | SURFACE AND THE BOTTOM OF THE | | SUPPORT RAIL. (AMENDED 1997 SMC | | 304.2.5) |
|