Plan Review Notes For Permit 01041075 |
Permit Number |
01041075 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-07-10 00:00:00 | 1) PLEASE PROVIDE MORE DETAILS ON | | PROPANE TANK SHOWN ON THE DRAWINGS. | | PLEASE INCLUDE TANK SIZE, PIPE SIZE, | | PHYSICAL PROTECTION, DISTANCES TO | | PROPERTY LINES, BUILDINGS, ETC. | | 2) NO FIRE SPRINKLER DRAWINGS PROVIDED | | WITH DRAWINGS. COMPLETE HYDRAULIC | | CALCULATIONS ALSO MISSING. | | 3) NO INFORMATION PROVIDED FOR OPTIONAL | | DAY CARE CENTER. | | 4) NO DETAILS PROVIDED ON GENERATOR. | | 5) NO DETAILS PROVIDED FOR THE INTERIOR | | OF PUBLIX STORE. | | 6) NO MECHANICAL,ELECTRICAL OR PLUMBING | | SHOWN FOR PUBLIX. | | 7) NO DETAILS PROVIDED FOR HOOD, DUCT | | AND EXTINGUISHING SYSTEMS. | | 8) BUILDING ADDRESS PLAN REVIEW COMMENTS | | NOT COMPLETELY CORRECT. THE RESPONSE | | DID NOT INCLUDE BUILDING ADDRESS ON | | THE ADDRESS SIDE OF THE BUILDINGS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|