Plan Review Notes
Plan Review Notes For Permit 01041075
Permit Number 01041075
Review Stop P
Sequence Number 1
Notes
Date Text
2001-05-11 00:00:00PLUMBING PLAN REVIEWDENIED
 REFERENCES STD PLBG CODE 94 STD GAS 97
 (1) SHT SP-1 SHOW LOCATION OF GREASE
 TANKS.
 (2) SHT P-1 RETAIL B,C DRINKING FOUNTAIN
 REQUIRED,EACH SPACE TAB 407.
 (3) SHT P-2,6 COMPLY WITH GAS APPLICAT-
 ION PERMT REQUIRMENTS,SEE ATTACHED.
 ESOV FOR BAKERY: MANUAL SOV TO BE UP
 STREAM OF UNION.
 (4) SHT P-4 SAFE WASTE NOT PERMITTED,
 EACH PLBG FIXTURE SHALL BE TRAPED,VENTED
 SEC 1001.8
 (5) SHT P-6 CONDENSATE DRAINS: ALL
 INDIRECT WASTE TO FLOOR SINKS SEC 802.
 (6) SHT P-6 DETAIL 8P-6 SANITIZER
 INSTALLERS ARE NOT LICENSED PLUMBERS.
 PLUMBER TO LEAVE A VALVED CONNECTION
 W/A WATTS 36-N ANTI SYPHON DEVICE FOR
 EACH SANITIZER CONNECTION TO POTTABLE
 WATER.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS561-659-8096 X 8233