Notes
Date Text
2001-05-23 00:00:00*******************PROVISO**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
  
 RETAIL "B" 01041078 & "C" 01041079
  
 1.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS AS PER NFPA
 90A 4-4.4.3.
  
 2.PVC FOR CONDENSATE ON ROOF TO COMPLY
 WITH MANUFACTURERS RECOMMENDATIOIN
 FOR UV TOLERANCE.
  
 PUBLIX STORE 01041075
  
 1.DRAWING A-9, DETAIL 11 - GREASE
 DUCT EXHAUST SHALL COMPLY WITH 1997
 SMC 506.1 FOR TERMINATION ABOVE
 ROOF (40" MIN. & 10' FROM ANY FRESH
 AIR INTAKES.)
  
 2.PLEASE PROVIDE AIR BALANCE SCHEDULE
 (1997 SMC 501.2)
  
 3.CLARIFY AC-4, IS IT CONDITIONING THE
 SPACE ABOVE THE CEILING?
  
 4.ADDITIONAL MECHANICAL PERMITS ARE
 REQUIRED FOR HOODS, FIRE SUPPRESSION
 FUEL AND WALK-IN COOLERS/FREEZERS.
 PLEASE SUBMIT PLANS AND MANUFACTURE
 CUT SHEETS AT THE TIME OF PERMIT
 APPLICATION.
  
 RETAIL "D"01041080
  
 NO PLANS SUBMITTED FOR THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.