Plan Review Notes For Permit 01041075 |
Permit Number |
01041075 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-05-23 00:00:00 | *******************PROVISO************** | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | WITH MECHANICAL PERMIT APPLICATION. | | | | RETAIL "B" 01041078 & "C" 01041079 | | | | 1.FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | WITH NOTIFICATION TO ALARM/STROBE IN | | NORMALLY OCCUPIED AREAS AS PER NFPA | | 90A 4-4.4.3. | | | | 2.PVC FOR CONDENSATE ON ROOF TO COMPLY | | WITH MANUFACTURERS RECOMMENDATIOIN | | FOR UV TOLERANCE. | | | | PUBLIX STORE 01041075 | | | | 1.DRAWING A-9, DETAIL 11 - GREASE | | DUCT EXHAUST SHALL COMPLY WITH 1997 | | SMC 506.1 FOR TERMINATION ABOVE | | ROOF (40" MIN. & 10' FROM ANY FRESH | | AIR INTAKES.) | | | | 2.PLEASE PROVIDE AIR BALANCE SCHEDULE | | (1997 SMC 501.2) | | | | 3.CLARIFY AC-4, IS IT CONDITIONING THE | | SPACE ABOVE THE CEILING? | | | | 4.ADDITIONAL MECHANICAL PERMITS ARE | | REQUIRED FOR HOODS, FIRE SUPPRESSION | | FUEL AND WALK-IN COOLERS/FREEZERS. | | PLEASE SUBMIT PLANS AND MANUFACTURE | | CUT SHEETS AT THE TIME OF PERMIT | | APPLICATION. | | | | RETAIL "D"01041080 | | | | NO PLANS SUBMITTED FOR THIS SECTION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|