Date |
Text |
2001-04-24 00:00:00 | 1) GENERAL NOTES ON PAGE A0.2 INDICATES |
| THE 2000 EDITION OF THE LIFE SAFETY |
| CODE. IT DEPENDS WHEN THE PERMIT IS |
| LET AND WHAT DISCUSSION HAVE OCCURRED |
| AS TO WHAT EDITION IS GOING TO BE USED. |
| EITHER THE 2000 OR THE 1985 EDITION. |
| 2) FIVE FIRE HYDRANTS LOCATED ON SITE |
| MAP. ADDITIONAL FIRE HYDRANTS MAY BE |
| REQUIRED BY THIS OFFICE. |
| 3) THE FIRE LANE MARKINGS AND SIGNAGE IS |
| TO BE APPROVED BY THIS OFFICE. |
| 4) KNOX-BOXES WILL BE REQUIRED. |
| 5) BUILDING ADDRESSES ARE REQUIRED FOR |
| ALL BUILDINGS LOCATED AT THE SITE PER |
| CITY CODE REQUIREMENTS. |
| 6) WET FIRE HYDRANTS MUST BE AVAILABLE |
| PRIOR TO AND DURING CONSTRUCTION.ALSO |
| SUITABLE ACCESS ROADS ARE TO BE |
| PROVIDED DURING CONSTRUCTION. |
| 7) PROVIDE SEPARATE PLANS AND PERMITS |
| FOR ANY HOOD, DUCT AND EXTINGUISHING |
| SYSTEMS PLANNED FOR COMMERCIAL |
| COOKING APPLICATIONS. |
| 8) PROVIDE SEPARATE PLANS AND PERMITS |
| FOR FIRE ALARM EQUIPMENT PLANNED FOR THE |
| BUILDINGS. |
| 9) NO FIRE SPRINKLER OR HYDRAULIC |
| CALCULATIONS PROVIDED WITH PLANS. THIS |
| INFORMATION IS REQUIRED PRIOR TO |
| RECEIVING A BUILDING PERMIT. |
| 10) TENANT DEMISING WALLS IN BUILDINGS |
| B AND C TO MEET BUILDING CODE |
| REQUIREMENTS. |
| 11) PLEASE EXPLAIN OPTIONAL DAY CARE |
| AREA FOR RETAIL BUILDING B. |
| 12) PLEASE PROVIDE DETAILS ON |
| EMERGENCY GENERATOR. PLEASE PROVIDE |
| INFORMATION ON ANY FUEL STORAGE FOR THE |
| GENERATOR. |
| 13) PLEASE PROVIDE MECHANICAL,ELECTRICAL |
| AND PLUMBING DRAWINGS FOR THE PUBLIX. |
| 14) PLEASE PROVIDE MORE INFORMATION |
| FOR THE INTERIOR OF THE PUBLIX STORE. |
| PLEASE PROVIDE A LIFE SAFETY PLAN |
| AND AN OCCUPANT LOAD DRAWING FOR THE |
| PUBLIX. |
| 15) ANY CHANGES IN ELEVATIONS LESS THAN |
| TWENTY ONE INCHES SHALL BE BY RAMPS. |
| 16) PLEASE SHOW ALL UNDERGOUND FIRE |
| MAINS, THEIR SIZES, CONNECTION POINTS, |
| BACKFLOW DEVICES, ETC. |
| |
| CAPTAIN MIKE CARSILLO |
| 659-8096,EXT.8497 |
| 835-2910 |