2001-05-10 00:00:00INDICATE CLEARLY ON THE SITE PLAN THE
 DISTANCE TO THE WEST PROPERTY LINE
  
 THE 3 HOUR RATED WALL REQUIRES 3 HOUR
 RATED OPENEINGS.
  
 SHOW A SPECIFIC FIRE DESIGN NUMBER FOR
 THE FIRE RATED WALL.
  
 WHAT IS THE NET CLEAR OPENING OF THE
 STOREFRONT DOORS?
  
 SHEET S1 SHOWS 7-93.SBC 97 INVOKES
 ASCE 7-95.
  
 SHOW THE HURRICANE MISSILE IMPACT
 PROTECTION.
  
 IMPACT FEES MUST BE PAID TO THE COUNTY.
 CALL 233-5025 FOR MORE INFORMATION.
  
 PROVIDE THE TEST DATA AND REPORTS FOR
 THE DOORS WINDOWS AND THE ROOF COVERING.
  
 PROVIDE A RECENT PROPERTY SURVEY.
  
 A RESIDENT INSPECTOR IS REQUIRED.
 CONTACT DON NEELY 561-659-8096 X 8333
 FOR MORE INFORMATION.