Plan Review Notes For Permit 01041075 |
Permit Number |
01041075 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-05-10 00:00:00 | INDICATE CLEARLY ON THE SITE PLAN THE | | DISTANCE TO THE WEST PROPERTY LINE | | | | THE 3 HOUR RATED WALL REQUIRES 3 HOUR | | RATED OPENEINGS. | | | | SHOW A SPECIFIC FIRE DESIGN NUMBER FOR | | THE FIRE RATED WALL. | | | | WHAT IS THE NET CLEAR OPENING OF THE | | STOREFRONT DOORS? | | | | SHEET S1 SHOWS 7-93.SBC 97 INVOKES | | ASCE 7-95. | | | | SHOW THE HURRICANE MISSILE IMPACT | | PROTECTION. | | | | IMPACT FEES MUST BE PAID TO THE COUNTY. | | CALL 233-5025 FOR MORE INFORMATION. | | | | PROVIDE THE TEST DATA AND REPORTS FOR | | THE DOORS WINDOWS AND THE ROOF COVERING. | | | | PROVIDE A RECENT PROPERTY SURVEY. | | | | A RESIDENT INSPECTOR IS REQUIRED. | | CONTACT DON NEELY 561-659-8096 X 8333 | | FOR MORE INFORMATION. |
|