2001-04-23 00:00:00******************DENIED****************
  
 PLANS WITH REFERENCED PERMIT #00120570,
 WHERE DENIED UNTIL THE FOLLOWING ITEMS
 ARE ADDRESSED.
  
 1.PROVIDE INFORMATION ON ZONES TO BE
 RUN IN A NEGATIVE PRESSURE, AIR
 BALANCE AND FAN OPERATION.
  
 2.PROVIDE INFORMATION ON VENTILATION
 FOR STORAGE ROOMS IN EVENT OF POWER
 FAILURE.
  
 3.PROVIDE INFORMATION ON DETECTION
 SYSTEM, BOTH NORMAL OPERATION AND IN
 THE EVENT OF A POWER FAILURE.
  
  
 PLEASE SUBMIT PLANS INCLUDING THE ABOVE
 INFORMATION.