Plan Review Notes
Plan Review Notes For Permit 01040897
Permit Number 01040897
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-30 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE NOT
 SIGNED AND SEALED BY THE ARCH/ENGINEERS
 OF RECORD PER 471.025/481.221 OF THE
 F.A.C..
  
 2)NOTE: PLEASE NOTE THAT PLANS ARE
 COMING BACK, PLEASE ADDRESS THE
 FOLLOWING COMMENTS.
  
 3) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 THERE ARE ROOMS SHOWING "FAN" J-BOX.
 PLEASE CLARIFY EGRESS LIGHTING.
  
 4)NOTE: PLEASE NOTE MISSING SMOKE DETECT
 OR INSIDE BEDRO0M #4. NFPA-72 2-2.1.1.1
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372