Plan Review Notes
Plan Review Notes For Permit 01040869
Permit Number 01040869
Review Stop P
Sequence Number 3
Notes
Date Text
2001-07-20 00:00:00PLUMBING PLAN,PROVISO
 PREVIOUS COMMENTS DATED 05-09-01
 (3) SHT P5-1 COMPLY WITH NFPA-99,CH-10
 LABORTORIES; ADDRESS EA. SEC.IN CH-10
 RE: HAZARDOUS MATERIALS PROCEDURE POLICY
 FOR THE STORAGE AND USE OF HAZARDOUS
 CHEMICALS. PROVIDE A OXYGEN DEPELETION
 ALARM.
 PREVIOUS COMMENT DATED 07-11-01
 (1) COMPLY WITH MFG MSDS REQUIRMENTS,
 SAFTEY SHOWERS WITH DRAINS (INSIDE BLDG)
 REQUIRED AS PER MFG.INSTRUCTIONS.
 (1) NEW COMMENT: REVISED PLANS BEFORE
 1ST ROUGH APPROVAL.
 (2) ALL WORK PER CITY CODES SUBJECT TO
 FIELD INSPECTOR APPROVAL.
 END OF COMMENTSPAUL SCHMITZ