2001-07-05 00:00:001) EXIT DOORS IN CAFETERIA 130 SWING
 IN THE WRONG DIRECTION. EXIT DOORS
 SHOULD SWING IN THE DIRECTION OF EXIT
 TRAVEL SINCE OCCUPANT LOAD IS NOTED TO
 BE 132 PERSONS. EVEN IF THE ROOM HAS 50
 OR MORE PERSONS, THE DOORS SHOULD SWING
 IN THE DIRECTION OF EXIT TRAVEL.
 2) DETAILS WERE PROVIDED FOR THE HOOD
 EXHAUST USED TO EXHUAST THE IONOX FUMES
 USED IN THE DEGREASER. IF THIS HOOD IS
 USED TO EXHUAST NOXIOUS GASES, FLAMMABLE
 OR CORROSIVE MATERIALS, THEN COMPLIANCE
 WITH SECTION 506 OF THE STANDARD
 MECHANICAL CODE, EXHUAST OUTLETS IS TO
 BE PROVIDED.
 3) TRAVEL DISTANCE SHOWN FROM THE
 MACHINE SHOP DOWN THE CORRIDOR INTO THE
 ASSEMBLY ROOM DOES NOT APPEAR TO BE THE
 MOST DIRECT ROUTE AND WOULD BE
 CONFUSING TO USE.
 4) PLEASE PROVIDE CHEMICAL LIST
 AMOUNTS TO THIS OFFICE.
  