Plan Review Notes
Plan Review Notes For Permit 01040869
Permit Number 01040869
Review Stop B
Sequence Number 2
Notes
Date Text
2001-07-16 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01040869
 2400 CENTERPARK W DRIVE
 SUITE # 100
 LEIGHTON MCGINN
 863-4455
  
 1)- SBC 903.1 APPROVED FIRE SPRINKLER
 EQUIPMENT, DEVICES AND LAYOUT OF THE
 COMPLETE SYSTEM.
  
 2)- SBC 308.2.2: CONTROL AREAS CONTAIN-
 ING HAZARDOUS MATERIAL NOT EXCEEDING THE
 EXEMPT QUANITIES SHALL BE PERMITTED IN
 ALL OCCUPANCIES. THE CONTROL AREAS SHALL
 BE SEPERATED BY 1-HR. FIRE RESISTANT
 CONSTRUCTION WITH 3/4 HR OPRNING PROTECT
 ION WITH SELF CLOSING OR AUTOMATIC CLOS-
 ING DEVICES IN ACCORDANCE WITH
 705.1.3.2.3. MACHINE SHOP, ASSEMBLY-138A
 AND ASSEMBLY 138B.
  
 3)- SBC T 308.2B: ALLOWABLE LIMIT OF
 CLASS 1-A FLAMMABLE/ COMBUSTIBLE LIQUIDS
 FOR A SPRINKLERED BLDG. NOT IN A CABINET
 IS 60 GAL./ CONTROL AREA.
  
 4)- CHIP SPIN AREA: SBC 308.2.3: WHEN
 STORED AMOUNTS OF ANY HAAZARDOUS MATER-
 IAL LISTED IN TABLES308.2A THROUGH
 308.2D IS EXCEEDED IN ANY ONE CONTROL
 AREA, SUCH STORAGE SHALL BE WITHIN A
 ROOM OR BUILDING CONFORMING TO THE CODE
 REQUIREMENTS FOR H2 OCCUPANCIES. 440 GAL
 OF HAZARDOUS MATERIALS ARE LOCATED IN
 THE CHIP SPIN AREA.
  
 5)- SBC TABLE 704.1.4 REQUIRES A 2HR.
 SEPERATION BETWEEN THE H2 OCCUPANCY AND
 THE FACTORY / MACHINE SHOP ( FACTORY OCC
 UPANCY).
  
 6)- SBC 407.1.3.4: HIGHLY TOXIC SOLIDS
 OR LIQUIDS: EXTERIOR STORAGE OF HIGHLY
 TOXIC SOLIDS OR LIQUIDS SHALL BE IN FIRE
 RESISTANT CONTAINERS OR SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
 1)- THE STORAGE AREA SHALL BE PROTECT-
 ED BY AN AUTOMATIC, OPEN HEAD, DELUGE
 SYSTEM OF THE TYPE AND DENSITY SPECIFIED
 IN NFPA 13 OR;
 2)- STORAGE SHALL BE UNDER A ROOF
 STRUCTURE OF NONCOMBUSTIBLE CONSTRUCTION
 WITH THE AREA UNDER THE ROOF PROTECTED
 BY AN AUTOMATIC FIRE EXTINGUISHING
 SYSTEM.
  
 7)- SBC 407.2.10: VISIBLE HAZARD
 IDENTIFICATION SIGNS AS SPECIFIED IN
 NFPA 704 SHALL BE PLACED AT ALL ENTRANCE
 TO LOCATIONS WHERE HAZARDOUS MATERIALS
 ARE STORED, DISPENSED USED OR HANDLED IN
 QUANITIES IN EXCESS OF THE EXEMPT
 AMOUNTS.
  
 8)- SBC 407.2.11: SECURITY DISPENSING,
 USE & HANDELING AREAS SHALL BE SECURED
 AGAINST UNATHORIZED ENTRY. STORAGE AREAS
 OF HIGHLY TOXIC AND TOXIC COMPRESSED
 GASSES SHALL BE SECURE AGAINST UNATHORIZ
 ED ENTRY.
  
 9)- CAFETERIA #130 60X32= 1920 SQ FT
 @ 15 FT/PER= 128 OCC. LOAD, GIVE SEATING
 ARRANGEMENT, > 50 PERSONS REQUIRES THE
 EGRESS DOORS TO SWING IN THE FLOW OF
 EXITING, SEE DOOR #40.
  
 10)- DOOR #30 FL ACCESSIBILITY 4.13.6
 REQUIRES MANEUVERING CLEARENCES AT DOORS
  
 11)- EITHER DOOR 30 OR 40 WILL BE REQUIR
 ED TO MEET THE EXITING REQUIREMENTS OF
 2 EXITS ONE WILL NEED TO MEET THE SWING
 REQUIREMENTS FOR EXITING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412