2001-07-16 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 01040869 |
| 2400 CENTERPARK W DRIVE |
| SUITE # 100 |
| LEIGHTON MCGINN |
| 863-4455 |
| |
| 1)- SBC 903.1 APPROVED FIRE SPRINKLER |
| EQUIPMENT, DEVICES AND LAYOUT OF THE |
| COMPLETE SYSTEM. |
| |
| 2)- SBC 308.2.2: CONTROL AREAS CONTAIN- |
| ING HAZARDOUS MATERIAL NOT EXCEEDING THE |
| EXEMPT QUANITIES SHALL BE PERMITTED IN |
| ALL OCCUPANCIES. THE CONTROL AREAS SHALL |
| BE SEPERATED BY 1-HR. FIRE RESISTANT |
| CONSTRUCTION WITH 3/4 HR OPRNING PROTECT |
| ION WITH SELF CLOSING OR AUTOMATIC CLOS- |
| ING DEVICES IN ACCORDANCE WITH |
| 705.1.3.2.3. MACHINE SHOP, ASSEMBLY-138A |
| AND ASSEMBLY 138B. |
| |
| 3)- SBC T 308.2B: ALLOWABLE LIMIT OF |
| CLASS 1-A FLAMMABLE/ COMBUSTIBLE LIQUIDS |
| FOR A SPRINKLERED BLDG. NOT IN A CABINET |
| IS 60 GAL./ CONTROL AREA. |
| |
| 4)- CHIP SPIN AREA: SBC 308.2.3: WHEN |
| STORED AMOUNTS OF ANY HAAZARDOUS MATER- |
| IAL LISTED IN TABLES308.2A THROUGH |
| 308.2D IS EXCEEDED IN ANY ONE CONTROL |
| AREA, SUCH STORAGE SHALL BE WITHIN A |
| ROOM OR BUILDING CONFORMING TO THE CODE |
| REQUIREMENTS FOR H2 OCCUPANCIES. 440 GAL |
| OF HAZARDOUS MATERIALS ARE LOCATED IN |
| THE CHIP SPIN AREA. |
| |
| 5)- SBC TABLE 704.1.4 REQUIRES A 2HR. |
| SEPERATION BETWEEN THE H2 OCCUPANCY AND |
| THE FACTORY / MACHINE SHOP ( FACTORY OCC |
| UPANCY). |
| |
| 6)- SBC 407.1.3.4: HIGHLY TOXIC SOLIDS |
| OR LIQUIDS: EXTERIOR STORAGE OF HIGHLY |
| TOXIC SOLIDS OR LIQUIDS SHALL BE IN FIRE |
| RESISTANT CONTAINERS OR SHALL COMPLY |
| WITH ONE OF THE FOLLOWING: |
| 1)- THE STORAGE AREA SHALL BE PROTECT- |
| ED BY AN AUTOMATIC, OPEN HEAD, DELUGE |
| SYSTEM OF THE TYPE AND DENSITY SPECIFIED |
| IN NFPA 13 OR; |
| 2)- STORAGE SHALL BE UNDER A ROOF |
| STRUCTURE OF NONCOMBUSTIBLE CONSTRUCTION |
| WITH THE AREA UNDER THE ROOF PROTECTED |
| BY AN AUTOMATIC FIRE EXTINGUISHING |
| SYSTEM. |
| |
| 7)- SBC 407.2.10: VISIBLE HAZARD |
| IDENTIFICATION SIGNS AS SPECIFIED IN |
| NFPA 704 SHALL BE PLACED AT ALL ENTRANCE |
| TO LOCATIONS WHERE HAZARDOUS MATERIALS |
| ARE STORED, DISPENSED USED OR HANDLED IN |
| QUANITIES IN EXCESS OF THE EXEMPT |
| AMOUNTS. |
| |
| 8)- SBC 407.2.11: SECURITY DISPENSING, |
| USE & HANDELING AREAS SHALL BE SECURED |
| AGAINST UNATHORIZED ENTRY. STORAGE AREAS |
| OF HIGHLY TOXIC AND TOXIC COMPRESSED |
| GASSES SHALL BE SECURE AGAINST UNATHORIZ |
| ED ENTRY. |
| |
| 9)- CAFETERIA #130 60X32= 1920 SQ FT |
| @ 15 FT/PER= 128 OCC. LOAD, GIVE SEATING |
| ARRANGEMENT, > 50 PERSONS REQUIRES THE |
| EGRESS DOORS TO SWING IN THE FLOW OF |
| EXITING, SEE DOOR #40. |
| |
| 10)- DOOR #30 FL ACCESSIBILITY 4.13.6 |
| REQUIRES MANEUVERING CLEARENCES AT DOORS |
| |
| 11)- EITHER DOOR 30 OR 40 WILL BE REQUIR |
| ED TO MEET THE EXITING REQUIREMENTS OF |
| 2 EXITS ONE WILL NEED TO MEET THE SWING |
| REQUIREMENTS FOR EXITING. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561) 659-8096 EX 8412 |