Plan Review Notes
Plan Review Notes For Permit 01040869
Permit Number 01040869
Review Stop P
Sequence Number 1
Notes
Date Text
2001-05-09 00:00:00PLUMBING PLAN REVIEWDENIED
 CODE REFERENCES SPC-94, NFPA-99 CH.10
 (1) SHT A-3 COMPLY WITH FACBC-97
 SEC.4.1.6 H/C ACCESSIBLE BUILDINGS
 SHOW ACCESSIBLE ROUTE,TURNING RADIUS,
 CLEAR FLOOR SPACE,IN ALL AREAS.
 EXECUTIVE OFFICE #114 ,TO BE H/C
 ADAPTABLE BACKING IN WALLS,SHO,NO CURB.
 (2) SHT P2.1 ENVIRO LAB, ALL INDIRECT
 WASTE TO FLOOF SINKS,SEC 802.
 (3) SHT P5.1 COMPLY W/NFPA-99 CH 10,
 LABORTORIES, ADDRESS EACH SECTION IN
 CHAPTER 10,RE: NITROGEN GAS. HAZARD,
 PROCEDURE POLICY,STORAGE AND TRANSFERE,
 QUANITY, ALARM FOR OXYGEN DEPELETION
 MSDS SHTS.
 (4) SHT P6.1 INFORMATION ON COMPRESSED
 AIR, LOCATION AND SOURCE OF COMPRESSED
 AIR.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096 X 8233