2001-05-09 00:00:00 | PLUMBING PLAN REVIEWDENIED | | CODE REFERENCES SPC-94, NFPA-99 CH.10 | | (1) SHT A-3 COMPLY WITH FACBC-97 | | SEC.4.1.6 H/C ACCESSIBLE BUILDINGS | | SHOW ACCESSIBLE ROUTE,TURNING RADIUS, | | CLEAR FLOOR SPACE,IN ALL AREAS. | | EXECUTIVE OFFICE #114 ,TO BE H/C | | ADAPTABLE BACKING IN WALLS,SHO,NO CURB. | | (2) SHT P2.1 ENVIRO LAB, ALL INDIRECT | | WASTE TO FLOOF SINKS,SEC 802. | | (3) SHT P5.1 COMPLY W/NFPA-99 CH 10, | | LABORTORIES, ADDRESS EACH SECTION IN | | CHAPTER 10,RE: NITROGEN GAS. HAZARD, | | PROCEDURE POLICY,STORAGE AND TRANSFERE, | | QUANITY, ALARM FOR OXYGEN DEPELETION | | MSDS SHTS. | | (4) SHT P6.1 INFORMATION ON COMPRESSED | | AIR, LOCATION AND SOURCE OF COMPRESSED | | AIR. | | END OF COMMENTS PAUL SCHMITZ | | QUESTIONS 561-659-8096 X 8233 |
|