Date Text
2001-05-11 00:00:00********************DENIED**************
  
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS AS PER ASHRAE 62-89.
  
 2.PLEASE PROVIDE AIR BALANCE SCHEDULE
 TO SHOW COMPLIANCE WITH 1997 SMC
 501.2.
  
 3.RTU 11 ON SCHEDULE INDICATES 3000
 CFM ON SCHEDULE AND PLAN TOTALS
 4020 CFM.SCHEDULE AND PLAN NEED
 TO CORRELATE.
  
 4.RTU 7A SCHEDULE INDICATES 3800 CFM
 PLAN REFLECTS 2330, A DIFFERENCE
 OF 1470 CFM.
  
 5.RTU 7 SCHEDULE 3200 CFM, PLAN 3310
 CFM.
  
 6.RTU 6 SCHEDULE 4200 CFM, PLAN 4700
 CFM.
  
 7.THE REST OF THE ROOF TOP UNITS THE
 SCHEDULE SHOWS MORE CFM'S THAN THE
 PLAN BUT ARE WITHIN RANGE.
  
 8.FIRE DAMPERS ON DRAWING M2.1 IN
 CORRIDOR 135A, ARE THEY FIRE
 DAMPERS OR FIRE/SMOKE DAMPERS?
  
 9.DRAWING M6.1, DETAIL FOR A/C ROOF
 EQUIPMENT, WE ARE UNDER THE
 STANDARD MECHANICAL CODE NOT THE
 SOUTH FLORIDA BUILDING CODE.
 CONDENDSER UNIT STAND SHALL COMPLY
 WITH THE AMENDED 1997 SMC 304.2.5,
 MINIMUM OF 18" FROM ROOF SURFACE TO
 THE BOTTOM OF C.U. SUPPORT RAIL.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 NOTE:MECHANICAL PLANS AND PERMIT ARE
 REQUIRED FOR CHILLER, CHILL WATER
 PIPING AND ANY EQUIPMENT SERVED
 BY CHILLED WATER.
  