Date |
Text |
2001-05-11 00:00:00 | ********************DENIED************** |
| |
| 1.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS AS PER ASHRAE 62-89. |
| |
| 2.PLEASE PROVIDE AIR BALANCE SCHEDULE |
| TO SHOW COMPLIANCE WITH 1997 SMC |
| 501.2. |
| |
| 3.RTU 11 ON SCHEDULE INDICATES 3000 |
| CFM ON SCHEDULE AND PLAN TOTALS |
| 4020 CFM.SCHEDULE AND PLAN NEED |
| TO CORRELATE. |
| |
| 4.RTU 7A SCHEDULE INDICATES 3800 CFM |
| PLAN REFLECTS 2330, A DIFFERENCE |
| OF 1470 CFM. |
| |
| 5.RTU 7 SCHEDULE 3200 CFM, PLAN 3310 |
| CFM. |
| |
| 6.RTU 6 SCHEDULE 4200 CFM, PLAN 4700 |
| CFM. |
| |
| 7.THE REST OF THE ROOF TOP UNITS THE |
| SCHEDULE SHOWS MORE CFM'S THAN THE |
| PLAN BUT ARE WITHIN RANGE. |
| |
| 8.FIRE DAMPERS ON DRAWING M2.1 IN |
| CORRIDOR 135A, ARE THEY FIRE |
| DAMPERS OR FIRE/SMOKE DAMPERS? |
| |
| 9.DRAWING M6.1, DETAIL FOR A/C ROOF |
| EQUIPMENT, WE ARE UNDER THE |
| STANDARD MECHANICAL CODE NOT THE |
| SOUTH FLORIDA BUILDING CODE. |
| CONDENDSER UNIT STAND SHALL COMPLY |
| WITH THE AMENDED 1997 SMC 304.2.5, |
| MINIMUM OF 18" FROM ROOF SURFACE TO |
| THE BOTTOM OF C.U. SUPPORT RAIL. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| NOTE:MECHANICAL PLANS AND PERMIT ARE |
| REQUIRED FOR CHILLER, CHILL WATER |
| PIPING AND ANY EQUIPMENT SERVED |
| BY CHILLED WATER. |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CONTACT |
| PATTY KRAUSS AT 659-8096 EXT. 8388. |