Plan Review Notes
Plan Review Notes For Permit 01040869
Permit Number 01040869
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-04-20 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. FIRE SPRINKLER DRAWINGS
 ARE REQUIRED PRIOR TO RECEIVING A
 BUILDING PERMIT.
 2) FIRE ALARM CIRCUITS TO BE CLASS A,
 STYLE D, NOT CLASS B, STYLE C AS
 REFLECTED IN THE FIRE ALARM NOTES
 SECTION. SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM SYSTEM
 INSTALLATION.
 3) PLEASE PROVIDE DETAILS ON NITROGEN
 TANK INSTALLATION.
 4) PLEASE PROVIDE DETAILS ON EXHAUST
 HOOD AND WHAT WILL IT BE USED FOR.
 5) PLEASE PROVIDE MORE DETAILS ON
 HEAT TREAT OVEN LOCATED IN ROOM 139.
 6) PLEASE PROVIDE DETAILS ON FURNACE
 LOCATED IN ROOM 136.
 7) PLEASE PROVIDE A LIFE SAFETY PLAN
 TO THIS OFFICE. THIS PLAN IS TO
 INCLUDE OCCUPANT LOAD CALCULATIONS AND
 TRAVEL DISTANCES TO EXITS.
 8) PLEASE SUBMIT A CHEMICAL LIST TO
 THIS OFFICE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910