Plan Review Notes For Permit 01040869 |
Permit Number |
01040869 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-04-24 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01040869 | | 2400 CENTERPARK W DRIVE | | LEIGHTON MCGINN | | 863-4455 | | | | 1)- LAY OUT OF OFFICE FURNITURE FOR ROOM | | 123A & B, MINIMUM ACCESS AISLES. | | | | 2)- CONTAINMENT DIKE: SIZE OF NITROGEN | | TANK IN LBS. OR GALLONS. SBC 407.2.3.4 | | TO MEET THE SECONDARY CONTAINMENT RE | | QUIREMENTS. | | | | 3)- SBC 104.2.2: MEDICAL GASSES WILL | | REQUIRE A SEPERATE PERMIT(COMPRESSED | | GASSES). | | | | 4)- SBC 407.1.3.5. LABORATORY HOODS: | | WHERE FLAMMABLE MATERIALS ARE TO BE USED | | SHALL REQUIRE A AUTOMATIC SPRINKLER | | SYSTEM. | | | | 5)- SBC 903.1 APPROVED FIRE SPRINKLER | | EQUIPMENT, DEVICES,AND LAYOUT OF THE | | COMPLETE SYSTEM. | | | | 6)- PREFABRICATED MEZZANINE STRUCTURE | | LOCATION MISSING ON THE FLOOR PLAN. LOCA | | TION OF STAIRS ISN'T CLEAR THERE IS | | EITHER A LANDING MISSING AT THE TOP OF | | THE STAIR OR BOTTOM. ATTACHED ARE SHEETS | | WITH REQUIREMENTS FOR MEZZANINES. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 EX 8412 |
|