Plan Review Notes
Plan Review Notes For Permit 01040868
Permit Number 01040868
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-05-16 00:00:00FAILED :
 1. PLEASE COORDINATE WITH CIVIL ENGINEER
 AND PUBLIC UTILITIES ENGINEERING
 SERVICES FOR ALL UNDERGROUND UTILITY
 CHANGES.WE BELIEVE THAT SOME CHANGES
 ARE BEING MADE THAT MAY AFFECT THIS SITE
 ALSO.
 2. SECTION A-A, SHEET 4 OF 9 SHOWS A 10'
 U.E ADJACENT TO WEST R/W, PLEASE VERIFY
 IF THIS 10' U.E STILL NEEDED.ALL
 UTILITY EASEMENT SHOULD BE APPROVED BY
 PUBLIC UTILITY ENGINEERING SERVICES.
 3. PLEASE PROVIDE DETAILS FOR DUMPSTER
 ENCLOSURES.SHEET A-1 REFERS TO SP-1,
 THIS SHEET IS NOT SUBMITTED.
 4. PLEASE PROVIDE PARKING STALL DETAILS
 DIMENSIONS FOR BOTH H.C AND NONE-H.C
 5. PROVIDE STORM WATER CALCULATION FOR
 OUR REVIEW IF YOU HAVE NOT SUBMITTED TO
 JOSE DEL RIO, STORM WATER ENGINEER AT
 1000 45TH STREET WEST PALM BEACH, FL
 33407.
 6. PERVIOUS & IMPERVIOUS CALCULATION
 MUST BE SHOWN ON PAVING AND DRAINAGE,
 THE TOTAL AMOUNT MUST EQUAL 100% OF
 TOTAL SITE ACRES OR S.F.PLEASE STATE
 EITHER ADDRESS OR PROPERTY CONTROL
 NUMBER.STORM WATER CHANGES WILL BE
 CALCULATED FROM THESE DATA.
 7. ANY WORK WITHIN PUBLIC R.O.W REQUIRES
 A SEPARATE PERMIT THROUGH OFFICE OF CITY
 ENGINEER.
 8. DEP PERMIT FOR UNDERGROUND UTILITY
 WORKS IS REQUIRED.
 9. PLEASE PROVIDE POLLUTION PREVENTION
 PLANS.PLAN SHOULD BE INSTALLED IN
 FIELD PRIOR TO ANY EARTH WORK.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492