2001-06-12 00:00:00IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. CALL 233-5025 FOR MORE
 INFORMATION.
  
 SHOW A DETAIL FOR THE B10 BEAM
 CONNECTION TO THE C2 COLUMNS.
  
 SHOW A CONSTRUCTION DETAIL FOR THE METAL
 STUD WALL DEPICTED IN SECTION S3/2.
 INCLUDE FASTENERS AND SPACING AS WELL
 AS WINDOW CONNECTION.
  
 NOTE THE ASSUMED SOIL BEARING VALUE.
  
 THE PAD FOOTING ON SHEET S1 GRID G4 IS
 NOT LABELED.
  
 SECTION 1 S/3 SHOWS A 12" LONG ANGLE
 SUPPORTING THE BAR JOIST WHICH WILL
 CONFLICT THE NOTED 2' OC SPACING OF THE
 ANCHOR BOLTS.
  
 S2 IN THE VICINITY OF GRID H & I 5 CALLS
 OUT AN ANGLE 3/8" THICK 8" LONG AND
 DOES NOT AGREE WITH S5 WHICH SHOWS A
 1/4" ANGLE APPARENTLY CONTINUOUS.
 PLEASE CLARIFY.
  
 PLEASE PROVIDE A RECENT SURVEY.IF THE
 PHASE I BUILDING IS ON THE SAME LOT SHOW
 THE OPENINGS IN THE FACING WALL SO THAT
 COMPLIANCE WITH SBC TABLE 600 MAY BE
 DETERMINED.