2001-05-30 00:00:00 | TRUSS DRAWINGS CHECKLIST: |
| 1-TRUSS ENGINEER TO PROVIDE ALL HIS |
| INFORMATION REQUIRED BY CHAPTER 61G15 |
| OF FLORIDA BOARD OF PROFESSIONAL |
| ENGINEERS AND CHAPTER 471 OF FLORIDA |
| STATUTES. |
| -PROVIDE INFO. ON TRUSS LAYOUT AS WELL. |
| 2-TRUSS GENERAL DRAWINGS: |
| -UPDATE DRAWINGS AS REQUIRED. SPECIFY |
| CODE AND DESIGN CRITERIA USED. |
| -(61G15-27): FOLLOW PROCEDURE TO SEAL |
| ANOTHER'S WORK. |
| -PROVIDE CLEAR, LEGIBLE AND UNCUT |
| COPIES. |
| 3-THERE IS ONLY ONE MEAN ROOF HEIGHT FOR |
| ENTIRE BUILDING. TABLE 1606.2A SBC/97. |
| 4-IF USING ASCE IT SHALL BE ASCE 7-95 |
| FOR 145MPH NOT ASCE 7-93 FOR 110MPH. |
| -COVER SHEET SAYS USING SBC/97. CLARIFY |
| -SOME TRUSSES ARE DESIGNED USING ASCE |
| AND OTHERS ARE USING SBC. CLARIFY. |
| 5-ARCHITECT TO REVIEW ALL TRUSS DRAWINGS |
| AFTER CORRECTIONS ARE DONE. |
| 6-TRUSS S15 WAS DESIGNED WITH THREE |
| BEARING POINTS. ARCHITECT TO SPECIFY |
| CONNECTOR AT MID BEARING POINT. |
| 7-ARCHITECT TO SPECIFY CONNECTOR THAT |
| MEETS THE UPLIFT LOADS CALCULATED ON |
| ENGINEERED TRUSSES S45, S46 AND T27. |
| |
| |
| |
| -THESE COMMENTS APPLY TO 01040803, |
| 01040806, 01040808 AND 01040810. |
| |