2001-05-30 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-TRUSS ENGINEER TO PROVIDE ALL HIS
 INFORMATION REQUIRED BY CHAPTER 61G15
 OF FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS AND CHAPTER 471 OF FLORIDA
 STATUTES.
 -PROVIDE INFO. ON TRUSS LAYOUT AS WELL.
 2-TRUSS GENERAL DRAWINGS:
 -UPDATE DRAWINGS AS REQUIRED. SPECIFY
 CODE AND DESIGN CRITERIA USED.
 -(61G15-27): FOLLOW PROCEDURE TO SEAL
 ANOTHER'S WORK.
 -PROVIDE CLEAR, LEGIBLE AND UNCUT
 COPIES.
 3-THERE IS ONLY ONE MEAN ROOF HEIGHT FOR
 ENTIRE BUILDING. TABLE 1606.2A SBC/97.
 4-IF USING ASCE IT SHALL BE ASCE 7-95
 FOR 145MPH NOT ASCE 7-93 FOR 110MPH.
 -COVER SHEET SAYS USING SBC/97. CLARIFY
 -SOME TRUSSES ARE DESIGNED USING ASCE
 AND OTHERS ARE USING SBC. CLARIFY.
 5-ARCHITECT TO REVIEW ALL TRUSS DRAWINGS
 AFTER CORRECTIONS ARE DONE.
 6-TRUSS S15 WAS DESIGNED WITH THREE
 BEARING POINTS. ARCHITECT TO SPECIFY
 CONNECTOR AT MID BEARING POINT.
 7-ARCHITECT TO SPECIFY CONNECTOR THAT
 MEETS THE UPLIFT LOADS CALCULATED ON
 ENGINEERED TRUSSES S45, S46 AND T27.
  
  
  
 -THESE COMMENTS APPLY TO 01040803,
 01040806, 01040808 AND 01040810.
  
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.