Plan Review Notes
Plan Review Notes For Permit 01040717
Permit Number 01040717
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-04-27 00:00:00FAILED:
 1. PLEASE PROVIDE STORM WATER
 CALCULATION FOR OUR REVIEW IF YOU HAVE
 NOT SUBMITTED TO JOSE DEL RIO, STORM
 WATER ENGINEER AT 1000 45TH STREET WEST
 PALM BEACH,FL 33407.
 2. PERVIOUS & IMPERVIOUS CALCULATION
 MUST BE SHOWN ON CIVIL PLAN, PLEASE
 STATE EITHER ADDRESS OR PROPERTY CONTROL
 NUMBER.
 3. PLEASE PROVIDE POLLUTION PREVENTION
 PLAN.THE POLLUTION PREVENTION PLAN
 MUST BE INSTALLED IN THE FIELD PRIOR TO
 ANY EARTHWORK.
 4. AN APPROVED BACKFLOW PREVENTER
 ASSEMBLY WILL NEED TO BE INSTALLED, IF
 NOT ALREADY IN PLACE AT THE POINT OF
 SERVICE ON PROPERTY.ALL BACKFLOW
 PREVENTERS SHALL BE COMPLETLY HIDDEN
 FROM VIEW WITH SHRUBS PRIOR TO
 ACTIVATION.
 5. A CLEAN-OUT WILL NEED TO BE INSTALLED
 IN THE SANITARY LATERAL, ON THE PROPERTY
 , AT THE BACK OF THE SIDEWALK, IF NOT
 ALREADY INSTALLED.
 6. ALL DRIVEWAY APPROACHES MUST BE (AT A
 MIN.) PER CITY STANDARD.SEE ATTACHED
 7. ALL GRADES FOR CITY SIDEWALKS MUST BE
 SET BY THE CITY SURVEY CREW, CALL 659-
 8040.
 8. DETAILS FOR EXFILTRATION TRENCH,
 SHOWS 2 IN. TYPE II ASPHALT, SECTION B-B
 SHOWS 1 1/2 IN. TYPE II, PLEASE VERIFY.
 8. PLEASE SPECIFY THICKNESS FOR
 SIDEWALKS.
 9. PLEASE REFER TO APPROPRIATE SHEET FOR
 HANDICAP PARKING SIGN DETAILS AND
 INSTALLATION.
 IF ANY QUESTION PLEASE CONTACT 561-659-
 8096 EXT. 8492.