Plan Review Notes For Permit 01040717 |
Permit Number |
01040717 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-04-26 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED TO | | BE SIGNED AND SEALED BY THE | | ARCHS/ENGINEER OF RECORD PER 417.025 | | AND 481.221 | | F.A.C. | | | | 2)NOTE: PLEASE NOTE THAT COLD WATER | | PIPE ISMISSING FROM GROUNDING | | ELECTRODE SYSTEM PER 250-50. | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | AIC RATING IS GIVEN FOR PANEL BUT NOT | | FOR MAIN. IS MAIN FUSED OR BRKR? | | | | 4)NOTE: PLEASE SEE ELECTRICAL PLAN | | SUBMITTED FOR SITE LIGHTING.E-5 | | PLANS SHOW ALL OUTSIDE EQUIPMENT AS | | NEMA-1(INDOOR). ALL EQUIPMENT NEEDS TO | | BE RATED FOR LOCATION OF ENVIROMENT. | | TYPE-O? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|