Plan Review Notes
Plan Review Notes For Permit 01040717
Permit Number 01040717
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-26 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED TO
 BE SIGNED AND SEALED BY THE
 ARCHS/ENGINEER OF RECORD PER 417.025
 AND 481.221
 F.A.C.
  
 2)NOTE: PLEASE NOTE THAT COLD WATER
 PIPE ISMISSING FROM GROUNDING
 ELECTRODE SYSTEM PER 250-50.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 AIC RATING IS GIVEN FOR PANEL BUT NOT
 FOR MAIN. IS MAIN FUSED OR BRKR?
  
 4)NOTE: PLEASE SEE ELECTRICAL PLAN
 SUBMITTED FOR SITE LIGHTING.E-5
 PLANS SHOW ALL OUTSIDE EQUIPMENT AS
 NEMA-1(INDOOR). ALL EQUIPMENT NEEDS TO
 BE RATED FOR LOCATION OF ENVIROMENT.
 TYPE-O?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372