Notes |
Date |
Text |
2001-04-25 00:00:00 | TEST AND OR PRODUCT ACCEPTANCE REPORTS | | FOR THE DOORS WINDOWS AND ROOF COVERING | | WILL BE REQUIRED WITH THE PERMIT. | | | | IF FIRE RATED PARTITIONS ARE INSTALLED A | | FIRE DESIGN NUMBER WILL BE NECESARY. | | SEE SBC 701.5 | | | | SECTION 6 A/5.0 TERMS SUCH AS "ANCHORED | | WITH APPROVED FASTENERS" ARE NOT AN | | ACCEPTABLE SUBSTITUTE FOR SPECIFIC | | DESIGN INFORMATION.SEE SBC 104.2. | | | | SECTION 1/S1SPECIFY ANCHOR BOLT LENGTH | | AND WELD SIZE. | | | | SHEET S 2.0SBC 1997 INVOKES ASCE 7-95 | | NOT 7-93. |
|