2001-10-05 00:00:00 | DENIED | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | 1) PLEASE GIVE OCCUPANT LOAD FOR EACH | | AREA. GIVE CALCULATIONS FOR MINIMUM FAC- | | ILITIES PER SPC TABLE 407. PAGE A-15 | | 2) PAGE A-15 GAS ISOMETRIC. VALVE RE- | | QUIRED BEFORE REGULATORS. PLEASE SHOW ON | | PLAN REVISION. | | 3) PAGE A-15 GAS ISOMETRIC. PLEASE PRO- | | VIDE MANUFACTURE INFO ON GAS W/HEATERS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|