2001-04-27 00:00:00 | *******************DENIED*************** | | | | MECHANICAL PERMIT REQUIRED PRIOR TO ANY | | WORK BEING DONE. | | | | PLEASE SUBMIT INFORMATION ON RTU-8, | | TONNAGE AND ANY OTHER EXISTING DROPS. | | INDICATE CFM'S BEING DISTRIBUTED. | | | | PRIOR TO CONNECTING TO ANY EXISTING | | DUCTWORK CALL FOR AN INSPECTION. | | | | PLEASE PROVIDE DETAIL ON DRYER BEING | | RELOCATED, SPECIFICALLY THE DRYER VENT | | LOCATION, SIZE AND TERMINATION. | | | | DRAWING A-3 SUPPLY DROP SHALL NOT BE | | LOCATED CLOSER THAN 3 FT TO THE SMOKE | | DETECTOR.(NFPA 72 2-5.2.1.7) |
|