Plan Review Notes
Plan Review Notes For Permit 01040625
Permit Number 01040625
Review Stop M
Sequence Number 1
Notes
Date Text
2001-04-27 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT REQUIRED PRIOR TO ANY
 WORK BEING DONE.
  
 PLEASE SUBMIT INFORMATION ON RTU-8,
 TONNAGE AND ANY OTHER EXISTING DROPS.
 INDICATE CFM'S BEING DISTRIBUTED.
  
 PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK CALL FOR AN INSPECTION.
  
 PLEASE PROVIDE DETAIL ON DRYER BEING
 RELOCATED, SPECIFICALLY THE DRYER VENT
 LOCATION, SIZE AND TERMINATION.
  
 DRAWING A-3 SUPPLY DROP SHALL NOT BE
 LOCATED CLOSER THAN 3 FT TO THE SMOKE
 DETECTOR.(NFPA 72 2-5.2.1.7)