Plan Review Notes
Plan Review Notes For Permit 01040625
Permit Number 01040625
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-04-19 00:00:001) THE NEW VESTIBULE SHOWN ON PAGE
 A-3 CREATES A DEAD-END CORRIDOR OF AT
 LEAST 34 FEET LONG.
 2) NO ILLUMINATED EXIT SIGN SHOWN ON
 PAGE A-1 QA RECORDS HALLWAY. IS THIS
 A DESIGNATED EXIT.
 3) IS THE BUILDING FIRE SPRINKLER
 PROTECTED. IF IT IS SOME ADJUSTMENTS
 WILL BE NEEDED TO ALTER SYSTEM TO
 NEW BUILDING MODIFICATIONS.
 4) THE SMOKE DETECTOR LOCATED IN THE
 EXISTING VESTIBULE APPEARS TO BE TOO
 CLOSE TO AIR CONDITIONING DIFFUSERS.
 CODE REQUIRES A MINIMUM OF THREE FEET
 FROM SMOKE DETECTORS TO AIR CONDITIONING
 DIFFUSERS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910