Plan Review Notes For Permit 01040625 |
Permit Number |
01040625 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-04-19 00:00:00 | 1) THE NEW VESTIBULE SHOWN ON PAGE | | A-3 CREATES A DEAD-END CORRIDOR OF AT | | LEAST 34 FEET LONG. | | 2) NO ILLUMINATED EXIT SIGN SHOWN ON | | PAGE A-1 QA RECORDS HALLWAY. IS THIS | | A DESIGNATED EXIT. | | 3) IS THE BUILDING FIRE SPRINKLER | | PROTECTED. IF IT IS SOME ADJUSTMENTS | | WILL BE NEEDED TO ALTER SYSTEM TO | | NEW BUILDING MODIFICATIONS. | | 4) THE SMOKE DETECTOR LOCATED IN THE | | EXISTING VESTIBULE APPEARS TO BE TOO | | CLOSE TO AIR CONDITIONING DIFFUSERS. | | CODE REQUIRES A MINIMUM OF THREE FEET | | FROM SMOKE DETECTORS TO AIR CONDITIONING | | DIFFUSERS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|