2001-04-17 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 I DID SEE THE NOTE DRAWN ON THE PLANS.
 HOWEVER, TRANSFORMERS ARE BEING CHANGED
 OUT EVERYDAY BY FPL AND WHAT EQUIPMNET
 WAS RATED FOR BEFORE MAY BE DIFFERENT AT
 THE PRESENT TIME. PLEASE SUBMIT AIC
 RATINGS FOR ALL NEW EQUIPMNET AND MAINS
 ETC.
 PLEASE SUBMIT THE ABOVE INFORMATION. IF
 THERE ARE ANY QUESTIONS OR IF CLARIFICAT
 ION IS NEEDED, PLEASE CALL.
  