Plan Review Notes
Plan Review Notes For Permit 01040612
Permit Number 01040612
Review Stop B
Sequence Number 1
Notes
Date Text
2001-04-19 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01040612
 1100 TECHNOLOGY PLACE SUITE 120
 HEDRICK BROTHERS
 689-8880
  
 1)- A COPY OF THE CODE COMMENTARY THAT
 PERTAINS TO CALCULATING AREA FOR A
 MEZZANINE IS ENCLOSED FOR REFRENCE, SEE
 AREA FOR OPEN AREA & AREA THAT IS
 ENCLOSED UNDER THE MEZZANINE.
 SBC 503.2.3.2. THE TOTAL SQ. FT. OF THE
 INTERIOR 24'-6" X 81'-9"= 2002.875 SQ FT
 CALC AREA MEZZANINE:
 29'-8"X24'-6"=726'
 12'-0"X16'-0"=192'
 TOTAL SQ FT918 SQ FT
  
 ALLOWABLE IF OPEN BELOW:
 2002.875'X .33%= 660.948 SQ FT
  
 ALLOWABLE AREA ENCLOSED:
 40'-6"X24'-6"=992.25X.33%=327.44 SQ FT
  
 2)- DISCREPANCIES:
 A)- SHEET A-1 MEZZANINE DETAIL: DEPICTS
 A DOOR ON THE MEZZANINE LEVEL SWING
 ING FROM AREA BELOW?
 B)- SHEET A-1 DEPICT 1ST FLOOR UNDER
 THE PROPOSED MEZZANINE AS FILE
 STORAGE WHERE AS S-3 FLOOR LOADS
 INDICATES THE UAS AS A OFFICE.
 C)- S-3 FLOOR LOADS ALSO INDICATES A
 CATWALK?
 D)- S-3 ALSO INDICATES THE MECH. ROOM
 AS 125 LBS. FLOOR LOAD BUT NOT THE
 MEZZANINE FLOOR.
  
 3)- THE TYPE OF STORAGE FOR THE PROPOSED
 MEZZANINE NEEDS TO BE DETERMINED:
 STORAGE SBC TABLE 204.1
 MODERATE HAZARD S1- 3 HR
 LOW HAZARDS2- 2 HR
 DEPENDING ON THE TYPE OF MATERIALS TO BE
 CLASSIFIED (S1/S2), WE MAY NEED TO
 ADDRESS THE TENANT SEPERATION WALLS,
 WHAT MATERIALS ARE THEY MADE OF?
  
 4)- ADMINISTRATIVE CODE/ CITY AMENDMENTS
 106.4.2 IT SHALL BE THE RESPONSIBLITY OF
 THE OWNER,AGENT,PROPREITOR OR OCCUPANT
 OF GROUP S & GROUP F OCCUPANCIES,OR ANY
 OCCUPANCY WHERE EXCESSIVE FLOOR LOADING
 IS LIKELY TO OCCUR, TO EMPLOY A COMPE-
 TANT ARCHITECT OR ENGINEER IN COMPUTING
 THE SAFE LOAD CAPACITY. ALL SUCH COMPU-
 TATIONS SHALL BE ACCOMPANIED BY AN AFFI-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE FLOOR LOAD ON EACH
 FLOOR IN POUNDS PER SQUARE FOOT UNIFORM-
 LY DISTRIBUTED. THE COMPUTATIONS AND AFF
 IDAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BUILDING DEPARTMENT.
  
 5)- ADMINISTRATIVE CODE/ CITY AMENDMENTS
 106.4.3. IN EVERY BUILDING OR PART OF
 BUILDING USED FOR STORAGE, THE SAFE
 FLOOR LOADS, AS REVIEWED BY THE BUILDING
 OFFICIAL ON THTE PLAN, SHALL BE MARKED
 ON PLATES OF APPROVED DESIGN WHICH SHALL
 BE SUPPLIED AND SECURELY AFFIXED BY THE
 OWNER OF THE BUILDING IN A CONSPICUOUS
 PLACE IN EACH STORY, TO WHICH THEY RE-
 LATE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412