Plan Review Notes For Permit 01040584 |
Permit Number |
01040584 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-05-24 00:00:00 | SBC 704.5.2 REQUIRES PARAPET WALLS FOR | | THIS CONSTRUCTION TYPE. | | | | CODE INFORMATION IS INCORRECT ON SHEET | | T1.REVISE TO SBC 1997 TERMS. | | | | WHAT WILL THIS BUILDING BE USED FOR? | | SEE SBC 104.1.5. | | | | WILL THE TYPE C2 COLUMN BE ADDED TO THE | | EXISTING WALLS? | | | | AREA SHOWN AS NEW GARAGE MUST COMPLY | | WITH SBC 411.2, AND SBC 411.4 OR 411.5 | | AS IS APPLICABLE. | | | | SBC 1997 INVOKES ASCE 7-95 NOT ASCE | | 7-93.REVISE AS NECESSARY. | | | | SHOW THE 2 HR FIRE RATED DESIGN NUMBER | | AND THE OPENING PROTECTIVES FOR THE | | EXTERIOR WALLS AS REQUIRED BY SBC TABLE | | 600 AND SBC 701.5.1. | | | | SHOW HOW THE BUILDING WILL BE MADE | | HANDICAP ACCESIBLE FROM THE PUBLIC | | RIGHT OF WAY.SEE THE FACBC. | | | | THE 2'-6" FRENCH DOORS DO NOT MEET | | EGRESS WIDTH OR HANDICAP.SEE SBC | | 1012.1 AND 4.13.1 (2) FACBC | | | | THE $15500.00 PERMIT VALUATION IS TOO | | LOW FOR THIS SCOPE OF WORK.PROVIDE | | ACOPY OF THE SIGNED CONTRACT AND A | | DETAILED TAKEOFF TO JUSTIFY THE | | VALUATION. |
|