Plan Review Notes For Permit 01040584
Permit Number 01040584
Review Stop B
Sequence Number 1
Notes
Date Text
2001-05-24 00:00:00SBC 704.5.2 REQUIRES PARAPET WALLS FOR
 THIS CONSTRUCTION TYPE.
  
 CODE INFORMATION IS INCORRECT ON SHEET
 T1.REVISE TO SBC 1997 TERMS.
  
 WHAT WILL THIS BUILDING BE USED FOR?
 SEE SBC 104.1.5.
  
 WILL THE TYPE C2 COLUMN BE ADDED TO THE
 EXISTING WALLS?
  
 AREA SHOWN AS NEW GARAGE MUST COMPLY
 WITH SBC 411.2, AND SBC 411.4 OR 411.5
 AS IS APPLICABLE.
  
 SBC 1997 INVOKES ASCE 7-95 NOT ASCE
 7-93.REVISE AS NECESSARY.
  
 SHOW THE 2 HR FIRE RATED DESIGN NUMBER
 AND THE OPENING PROTECTIVES FOR THE
 EXTERIOR WALLS AS REQUIRED BY SBC TABLE
 600 AND SBC 701.5.1.
  
 SHOW HOW THE BUILDING WILL BE MADE
 HANDICAP ACCESIBLE FROM THE PUBLIC
 RIGHT OF WAY.SEE THE FACBC.
  
 THE 2'-6" FRENCH DOORS DO NOT MEET
 EGRESS WIDTH OR HANDICAP.SEE SBC
 1012.1 AND 4.13.1 (2) FACBC
  
 THE $15500.00 PERMIT VALUATION IS TOO
 LOW FOR THIS SCOPE OF WORK.PROVIDE
 ACOPY OF THE SIGNED CONTRACT AND A
 DETAILED TAKEOFF TO JUSTIFY THE
 VALUATION.