Plan Review Notes
Plan Review Notes For Permit 01040525
Permit Number 01040525
Review Stop R
Sequence Number 1
Notes
Date Text
2001-05-01 00:00:00************BUILDING PROVISO************
  
 1. PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 SBC 104.2.2
  
 2. ENERGY CALCULATIONS NOT AS PER PLANS
 ENERGY FORM SHOWS 3760' UNDER ATTIC.
 PLANS SHOW 4595' UNDER ATTIC
 CORRECT ENERGY FORMS AND RESUBMIT.
 3. PG. C-1 COVER SHEET ITEM #4 FRAMING
 NOTES:
 TRUSS MFGR SHALL SUBMIT THREE (3)
 COPIES OF SHOP DRAWINGS AND ENGINEERING
 CALCULATIONS SIGNED & SEALED BY A FLA
 REGISTERED ENGINEER OF THEIR ROOF TRUSS
 DESIGN FOR APPROVAL INCLUDING TWO (2)
 COPIES FOR ARCHITECTS' REVIEW PRIOR TO
 FABRICATION.TWO COPIES OF THE SIGNED
 AND SEALED TRUSS DRAWINGS APPROVED BY
 THE ARCHITECT SHALL BE SUBMITTED PRIOR
 TO INSTALLATION OF TRUSSES.
 4. RADON FEES TOTAL$45.96