Plan Review Notes For Permit 01040479 |
Permit Number |
01040479 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-10-19 00:00:00 | DENIED | | REFERENCE: SPC-94 - FHA-AMEND-98 DESIGN | | MANUAL. | | 1) SHEET A1.0 CODE ANALYSIS/BLDG DATA. | | FHA-98 D. MANUAL - STILL REQUIRED TO | | SPECIFY "A" OR "B", NOT A AND B AS STAT- | | ED. | | 2) SHEEET P1 WATER RISER DIAGRAMS. AIR | | CHAMBERS SHALL COMPLY WITH SPC-94 SEC. | | 607.8.3 ACCESSIBLE & RECHARGEABLE. IF | | WATER HAMMER ARRESTORS ARE USED THEY | | WILL BE SIZED AND LOCATED PER MANUFACT- | | URE'S INSTALLATION INSTRUCTIONS AND PER | | WH-PDI 201. | | 3) PAGE P-1 WATER RISER DIAGRAM TYPICAL. | | MAXIMUM FIXTURES ON 1/2" COLD IS 2 FIX- | | TURES. MODEL COUNTYWIDE AMENDMENTS TO | | SPC-94 SEC 607.7 | | 4) PAGE P-2, P/T #1 ON FLOOR PLAN SHOWS | | 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS | | A SINGLE RISER. TWWO RISERS ARE REQUIRED | | SPC-94 SEC 507.8.2 & 507.8.4. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|