2001-10-19 00:00:00DENIED
 REFERENCE: SPC-94 - FHA-AMEND-98 DESIGN
 MANUAL.
 1) SHEET A1.0 CODE ANALYSIS/BLDG DATA.
 FHA-98 D. MANUAL - STILL REQUIRED TO
 SPECIFY "A" OR "B", NOT A AND B AS STAT-
 ED.
 2) SHEEET P1 WATER RISER DIAGRAMS. AIR
 CHAMBERS SHALL COMPLY WITH SPC-94 SEC.
 607.8.3 ACCESSIBLE & RECHARGEABLE. IF
 WATER HAMMER ARRESTORS ARE USED THEY
 WILL BE SIZED AND LOCATED PER MANUFACT-
 URE'S INSTALLATION INSTRUCTIONS AND PER
 WH-PDI 201.
 3) PAGE P-1 WATER RISER DIAGRAM TYPICAL.
 MAXIMUM FIXTURES ON 1/2" COLD IS 2 FIX-
 TURES. MODEL COUNTYWIDE AMENDMENTS TO
 SPC-94 SEC 607.7
 4) PAGE P-2, P/T #1 ON FLOOR PLAN SHOWS
 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS
 A SINGLE RISER. TWWO RISERS ARE REQUIRED
 SPC-94 SEC 507.8.2 & 507.8.4.
  