Plan Review Notes For Permit 01040479 |
Permit Number |
01040479 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-10-01 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01040479 | | BLDG "A" | | 605 EXECUTIVE CENTER DR | | | | REVISIONS : CITY RECEIVED DATE 9/20/01 | | 1)- SHEET A2.0 MISING RED LINE NOTE FOR | | TRASH ROOM | | | | 2)- SHEET A2.3 DETAIL #8 SBC 1608.2.2.3 | | SHOW COMPLIANCE WITH GAURD RAIL TO | | RESIST 200 LBS CONCENTRATED HORIZONTAL | | LOADS APPLIED ON A 1 FT SQ AREA. AT ANY | | POINT IN THE SYSTEM INCLUDING INTERMED- | | IATE RAILS OR OTHER ELEMENTS SERVING | | THIS PURPOSE. | | | | 3)- SHEET A.6 MISSING RED LINE CORREC- | | TIONS, | | A)- ROOFING COMMENTS | | B)- ROOF A/C AIR HANDLERS & SUP- | | PORTS MIN. 18" CLEARENCE IS | | MISSING. | | C)- A/C CLOSET - INCREASE THE DOOR | | HEIGTH FOR FULL ACCESS. | | | | 4)- SHEET #7 NOTE MISSING DETAIL #2, | | FLOOR DRAINS, INACTUALLITY, OVERFLOW | | SCUPPERS (SBC 1517.6.4.3) NOT LESS THAN | | 2" ABOVE THE ROOF DECK NOR 4" MAXIMUM. | | | | 5)- SHEET A8.1 IS MISING RED LINE CORREC | | TIONS TO THE FAIR HOUSING ACT. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 X 8412 |
|