Plan Review Notes
Plan Review Notes For Permit 01040479
Permit Number 01040479
Review Stop P
Sequence Number 3
Notes
Date Text
2001-09-28 00:00:00DENIED
 REFERENCE: SPC-94 - FHA-98
  
 1) SHEET A1.0 CODE ANALYSIS/BLDG DATA.
 FHA-REVISED 1998 DESIGN MANUAL ADDRESS
 REQUIREMENTS 1 THRU 7 - SPECIFY "A" OR
 "B" OPTION.
 2) SHEET A8.1 DETAIL MENS ROOM URNAL TO
 BE 17" AFF TO LIP. FACBC-98 4.18.2
 3) SHEET A8.1 KITCHENETTE SINK TO BE
 34"TO COUNTER TOP. FACBC-98 4.24
 4) SHEET P-1 WATER RISER DIAGRAMS. AIR
 CHAMBERS SHALL COMPLY WITH SPC-94 SEC
 607.8.3 ACCESSIBLE & RECHARGEABLE. IF
 WATER HAMMER ARRESTORS ARE USED THEY
 WILL BE SIZED AND LOCATED PER MANUFACT-
 URES INSTALLATION INSTRUCTIONS AND PER
 WH-PDI 201.
 5) PAGE P-1 WATER RISER DIAGRAM TYPICAL.
 MAXIMUM FIXTURES ON 1/2" COLD IS 2 FIX-
 TURES. MODEL COUNTRWIDE AMENDMENTS TO
 SPC-94 SEC 607.7
 6) PAGE P-2, P/T #1 ON FLOOR PLAN SHOWS
 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS
 A SINGLE RISER. TWO RISERS ARE REQUIRED.
 SPC-94 SEC 507.8.2 & 507.8.4
 7) PAGE A8.1 BACKING AT TUB TO BE 1'5"
 NOT 1'2" AS SHOWN. FHA-98 REQUIREMENT 6.
 PLEASE SHOW ALL BACKING WITH CORRECT
 DISTANCE OFF FLOOR WITH CORRECT LENGTH
 AND WIDTH SHOWN.
  
 REVIEW KEN STEVENS
 (561) 659-8096 EXT. 8377