2001-05-01 00:00:00 | 1) ALL UNDERGROUND FIRE MAINS ARE TO BE |
| LISTED FOR FIRE PROTECTION SERVICE AND |
| COMPLY WITH NFPA 24, FIRE SERVICE MAINS |
| AND THEIR APPURTENANCES. |
| 2) INGRESS AND EGRESS INTO THE COMPLEX |
| SHALL BE A MINIMUM OF TWENTY FEET IN |
| CLEAR WIDTH. BATTERY BACK-UP FEATURE |
| SHALL BE PROVIDED FOR GATE-ARMS SHOULD |
| LOSS OF POWER OCCUR. TRAFFIC CALMING |
| HUMPS ARE NOT TO INTERFERE WITH FIRE |
| RESCUE MOVEMENT INTO THE COMPLEX. |
| 3) BUILDING LETTERS A,B,C,AND D, ARE TO |
| BE PLACED ON THE BUILDINGS SINCE IT |
| APPEARS TO BE A SINGLE ADDRESS FOR THE |
| APARTMENT COMPLEX. |
| 4) AT LEAST ONE STAIR IS TO BE |
| PROVIDED AT EACH BUILDING DURING |
| CONSTRUCTION. TEMPORARY STANDPIPES ARE |
| REQUIRED IN ALL BUILDINGS UNDER |
| CONSTRUCTION WHEN THEY ARE REQUIRED TO |
| HAVE STANDPIPE SYSTEMS. |
| 5) HOW IS COMBUSTIBLE LINT REMOVED FROM |
| THE DRYER CHASE. NO ACCESS PANELS HAVE |
| BEEN PROVIDED. |
| 6) PROVIDE SEPARATE PLANS AND PERMITS |
| FOR THE INSTALLATIONS OF THE FIRE |
| SPRINKLER SYSTEMS. NO HYDRAULIC |
| CALCULATIONS PROVIDED WITH SPRINKLER |
| DRAWINGS. STANDPIPE SYSTEMS ARE REQUIRED |
| IN ALL BUILDINGS THREE STORIES AND MORE |
| THAN FIFTY FEET IN HEIGHT. ALL VERTICAL |
| SHAFTS ARE TO BE FIRE SPRINKLER |
| PROTECTED. PLEASE EXPLAIN RATIONALE FOR |
| SINGLE FIRE DEPARTMENT CONNECTION SHOWN |
| ON THE DRAWINGS. |
| 7) DOOR SWINGS IN STAIRWELLS ARE TO |
| SWING IN THE DIRECTION OF EXIT TRAVEL. |
| 8) SMOKE DETECTORS WHEN INSTALLED ARE |
| TO BE A MINIMUM OF THREE FEET FROM |
| AIR CONDITIONER DIFFUSERS. |
| 9) TRASH CHUTES TO COMPLY WITH NFPA 82, |
| STANDARD ON INCINERATORS, WASTE AND |
| LINEN HANDLING SYSTEMS AND EQUIPMENT. |
| 10) PLEASE INDICATE PORTABLE FIRE |
| EXTINGUISHER LOCATIONS. |
| 11)SIGNS ARE REQUIRED FOR ALL |
| BUILDINGS FOUR OR MORE STORIES. SIGNS |
| SHALL INDICATE FLOOR LEVEL, THE IDENTITY |
| OF THE STAIR, THE TERMINUS OF THE STAIR, |
| TOP AND BOTTOM. |
| 12) PROVIDE SEPARATE PLANS AND PERMITS |
| FOR THE FIRE ALARM SYSTEM. |
| |