Plan Review Notes
Plan Review Notes For Permit 01040473
Permit Number 01040473
Review Stop B
Sequence Number 1
Notes
Date Text
2001-04-18 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01040473
 L DAVIS CONST
 848-0577
  
 1)- THE SURVEY INDICATES THAT THE EAST
 SIDE OF THE BUILDING IS A PROPERTYLINE.
 SBC TABLE 600 0'- 3'-0" FROM THE PROPER-
 TY LINE DOESN'T ALLOW FOR OPENINGS IN
 THE WALL.
  
 2)- THE EPS CORNICE AND TRIM DEPICTED ON
 SHEET A-4 IS REQUIERED TO MEET THE NON-
 COMBUSTIBLE REQUIREMENTS FOR ARCHITEC-
 TURAL TRIM FOR BUILDINGS LOCATED WITHIN
 A DESIGNATED FIRE DISTRICT.
  
 3)- FLORIDA ACCESSIBILITY CODE 4.1.3
 VERTICAL ACCESSIBILITY:
 4.1.6 (ALTERATIONS) (A) NO ALTERATION
 SHALL BE UNDERTAKEN WHICH DECREASES OR
 HAS THE EFFECT OF DECREASING ACCESIBIL-
 ITY OR USABILITY OF A BUILDING OR
 FACILITY BELOW THE REQUIREMENTS FOR NEW
 CONSTRUCTION AT THE TIME OF ALTERATION.
  
 THE 4TH FLOOR NEEDS TO BE MADE ACCESS-
 IBLE FOR THE HANDICAPPED BY EITHER AN
 ELEVATOR OR APPROVED PLATFORM LIFT.
 SEE 4.10 / ELEVATORS, 4.11 PLATFORM LIFT
 OF FL ACCESSIBILITY CODE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412