Plan Review Notes
Plan Review Notes For Permit 01040463
Permit Number 01040463
Review Stop M
Sequence Number 1
Notes
Date Text
2001-04-24 00:00:00******************DENIED****************
  
 PLEASE PROVIDE O.A. CALCULATION AS PER
 ASHRAE 62-89.
  
 PLEASE CLARIFY "REMOTE STATUS INDICATOR"
 FOR DUCT SMOKE DETECTOR.WILL THIS BE
 TIED TO A CONSTANTLY ATTENDED LOCATION?
 (NFPA 90A 4-4.4.2)
  
  
 NOTE:CONDENSER WATER PIPING WITH TYPE
 "K" COPPER SHALL BE BRAZED AS
 PER 1997 SMC TABLE 1205.