2001-04-17 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY GROUNDING OF
 TRANSFORMER. PER 250,450-5
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 AND SHOW COMPLETED KVA LOADS PER 215-5
 ANDART:220 AND SHOW ALL CONTINUOUS
 LOADS AT125% PER 215-2-3,220-4
  
 3)NOTE: PLEASE LABEL TRANSFORMER IN
 ELECROOM, SO THAT ALL REQ`MENTS OF
 240-21 ARE MET.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372