Plan Review Notes For Permit 01040463 |
Permit Number |
01040463 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-04-17 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: PLEASE CLARIFY GROUNDING OF | | TRANSFORMER. PER 250,450-5 | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS | | AND SHOW COMPLETED KVA LOADS PER 215-5 | | ANDART:220 AND SHOW ALL CONTINUOUS | | LOADS AT125% PER 215-2-3,220-4 | | | | 3)NOTE: PLEASE LABEL TRANSFORMER IN | | ELECROOM, SO THAT ALL REQ`MENTS OF | | 240-21 ARE MET. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE NAY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|