Plan Review Notes
Plan Review Notes For Permit 01040428
Permit Number 01040428
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-04-20 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS.
 2) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE FIRE
 SPRINKLER SYSTEM.
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE FIRE ALARM
 SYSTEM.
 4) A KNOX-BOX RAPID ENTRY SYSTEM WILL
 BE REQUIRED FOR FIRE RESCUE PURPOSES.
 APPLICATIONS CAN BE OBTAINED FROM FIRE
 RESCUE, 835-2910.
 5) NO EMERGENCY LIGHTING FIXTURES
 SHOWN.
 6) PLANS ARE TO BE SUBMITTED FOR TENANT
 REMODEL PRIOR TO BEGINNING WORK.
 7) DUCT SMOKE DETECTORS ARE REQUIRED IN
 AIR HANDLING SYSTEMS OVER 2000 CFM. WHEN
 ACTIVATED, THEY ARE TO SHUT DOWN AIR
 HANDLING EQUIPMENT AND ACTIVATE THE
 BUILDINGS FIRE ALARM SYSTEM.
 8) DURING CONSTRUCTION, FIRE HYDRANTS
 AND SUITABLE ROADS TO ACCESS THE
 PROPERTY ARE TO BE PROVIDED DURING
 CONSTRUCTION.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910