Plan Review Notes For Permit 01040428 |
Permit Number |
01040428 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-04-20 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | CODE REQUIREMENTS. | | 2) PROVIDE SEPARATE PLANS AND PERMITS | | FOR THE INSTALLATION OF THE FIRE | | SPRINKLER SYSTEM. | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | FOR THE INSTALLATION OF THE FIRE ALARM | | SYSTEM. | | 4) A KNOX-BOX RAPID ENTRY SYSTEM WILL | | BE REQUIRED FOR FIRE RESCUE PURPOSES. | | APPLICATIONS CAN BE OBTAINED FROM FIRE | | RESCUE, 835-2910. | | 5) NO EMERGENCY LIGHTING FIXTURES | | SHOWN. | | 6) PLANS ARE TO BE SUBMITTED FOR TENANT | | REMODEL PRIOR TO BEGINNING WORK. | | 7) DUCT SMOKE DETECTORS ARE REQUIRED IN | | AIR HANDLING SYSTEMS OVER 2000 CFM. WHEN | | ACTIVATED, THEY ARE TO SHUT DOWN AIR | | HANDLING EQUIPMENT AND ACTIVATE THE | | BUILDINGS FIRE ALARM SYSTEM. | | 8) DURING CONSTRUCTION, FIRE HYDRANTS | | AND SUITABLE ROADS TO ACCESS THE | | PROPERTY ARE TO BE PROVIDED DURING | | CONSTRUCTION. | | | | APPROVED PROVISO: | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|