Plan Review Notes
Plan Review Notes For Permit 01040428
Permit Number 01040428
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-04-24 00:00:00FAILED:
 1. PERVIOUS & IMPERVIOUS CALCULATIONS
 MUST BE SHOWN ON PAVING AND DRAINAGE
 PLAN, THE TOTAL AMOUNT MUST EQUAL 100 %
 OF TOTAL SITE ACRES OR S.F.PLEASE
 STATE EITHER ADDRESSES OR PROPERTY
 CONTROL NUMBER.STORM WATER CHARGES
 WILL BE CALCULATED FROM THESE.
 2. PLEASE PROVIDE STORM WATER
 CALCULATION FOR OUR REVIEW IF YOU HAVE
 NOT SUBMITTED TO JOSE DEL RIO, STORM
 WATER ENGINEER, 1000 45TH STREET WEST
 PALM BEACH, FL 33407. PLEASE SEE
 ATTACHED
 3. ONCE REVISED, TWO SETS OF PLANS MUST
 BE SUBMITTED TO PUBLIC UTILITIES
 ENGINEERING SERVICES FOR THIER REVIEW
 AND ACTUAL SERVICE CONNECTIONS.
 4. WORK PERFORMED ALONG PUBLIC R.O.W
 REQUIRES A PERMIT THROUGH CITY ENGINEERS
 OFFICE, RICHARD PITTMAN.
 1000 45TH STREET WEST PALM BEACH, FL
 33407
 5. PLEASE VERIFY SECTION A-A AS SHOWN ON
 SHEET 5 OF 10.IS THERE A 10' UTILITY
 EASEMENT ON THAT SIDE? IF SO,PLEASE SHOW
 6. PLEASE COORDINATE WITH PUBLIC
 UTILITIES ENGINEERING SEVICES DEPARTMENT
 FOR CONNECTION OF SERVICES (WATER,
 SANITARY).PERHAPS YOU COULD ELIMINATE
 THE 30' U.E IN PARKING AREA BY OTHER
 ALTERNATIVE SUCH AS INSTALLING 8" DIP
 AND SANITARY ALONG BRISTOL DRIVE GOING
 SOUTH AND THEN CONNECTING TO THE
 EXISTINGS ON SOUTHSIDE OF PROPERTY.
 THIS WILL LOCATE THE BACKFLOW PREVENTERS
 ON BACK OF SIDEWALK AND PROPERTY LINES.
 A MEETING WITH PUBLIC UTILITIES
 ENGINEERING SERVICES IS RECOMMENDED.