2001-04-24 00:00:00 | FAILED: |
| 1. PERVIOUS & IMPERVIOUS CALCULATIONS |
| MUST BE SHOWN ON PAVING AND DRAINAGE |
| PLAN, THE TOTAL AMOUNT MUST EQUAL 100 % |
| OF TOTAL SITE ACRES OR S.F.PLEASE |
| STATE EITHER ADDRESSES OR PROPERTY |
| CONTROL NUMBER.STORM WATER CHARGES |
| WILL BE CALCULATED FROM THESE. |
| 2. PLEASE PROVIDE STORM WATER |
| CALCULATION FOR OUR REVIEW IF YOU HAVE |
| NOT SUBMITTED TO JOSE DEL RIO, STORM |
| WATER ENGINEER, 1000 45TH STREET WEST |
| PALM BEACH, FL 33407. PLEASE SEE |
| ATTACHED |
| 3. ONCE REVISED, TWO SETS OF PLANS MUST |
| BE SUBMITTED TO PUBLIC UTILITIES |
| ENGINEERING SERVICES FOR THIER REVIEW |
| AND ACTUAL SERVICE CONNECTIONS. |
| 4. WORK PERFORMED ALONG PUBLIC R.O.W |
| REQUIRES A PERMIT THROUGH CITY ENGINEERS |
| OFFICE, RICHARD PITTMAN. |
| 1000 45TH STREET WEST PALM BEACH, FL |
| 33407 |
| 5. PLEASE VERIFY SECTION A-A AS SHOWN ON |
| SHEET 5 OF 10.IS THERE A 10' UTILITY |
| EASEMENT ON THAT SIDE? IF SO,PLEASE SHOW |
| 6. PLEASE COORDINATE WITH PUBLIC |
| UTILITIES ENGINEERING SEVICES DEPARTMENT |
| FOR CONNECTION OF SERVICES (WATER, |
| SANITARY).PERHAPS YOU COULD ELIMINATE |
| THE 30' U.E IN PARKING AREA BY OTHER |
| ALTERNATIVE SUCH AS INSTALLING 8" DIP |
| AND SANITARY ALONG BRISTOL DRIVE GOING |
| SOUTH AND THEN CONNECTING TO THE |
| EXISTINGS ON SOUTHSIDE OF PROPERTY. |
| THIS WILL LOCATE THE BACKFLOW PREVENTERS |
| ON BACK OF SIDEWALK AND PROPERTY LINES. |
| A MEETING WITH PUBLIC UTILITIES |
| ENGINEERING SERVICES IS RECOMMENDED. |