Plan Review Notes
Plan Review Notes For Permit 01040393
Permit Number 01040393
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-06-25 00:00:001) ACCORDING TO WEITZ PERSONNEL, THE
 EXISTING GATE LOCATED ON JEFFERSON ROAD
 IS EXISTING AND NOT EQUIPPED WITH ANY
 PROVISIONS FOR OPENING IT WHEN LOSS OF
 POWER OCCURS. IT WAS REPORTED THAT THE
 GATES ARE FAIL SECURE. THE FDC AND THE
 HYDRANT SHOULD BE LOCATED ON THE SAME
 SIDE OF THE SECURITY FENCE. IF THE
 PRESENT SECURITY FENCE IS NOT MODIFIED
 THEN THESE DEVICES SHOULD BE LOCATED
 OUTSIDE OF IT.
 2) COULD NOT LOCATE CODE SECTION 5-12
 REGARDING SINGLE EXIT AND TRAVEL
 DISTANCE OF 100 FEET. PLEASE PROVIDE
 APPLICABLE CODE SECTION.
 3) EIGHTEEN FEET MUST BE PROVIDED FROM
 FIRE HYDRANTS TO ANY OBSTRUCTIONS PER
 CITY CODE REQUIREMENTS.
 4) PLEASE PROVIDE MORE DETAILS ON
 EMERGENCY GENERATOR.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910