2 |
|
Notes |
Date |
Text |
2001-06-25 00:00:00 | 1) ACCORDING TO WEITZ PERSONNEL, THE | | EXISTING GATE LOCATED ON JEFFERSON ROAD | | IS EXISTING AND NOT EQUIPPED WITH ANY | | PROVISIONS FOR OPENING IT WHEN LOSS OF | | POWER OCCURS. IT WAS REPORTED THAT THE | | GATES ARE FAIL SECURE. THE FDC AND THE | | HYDRANT SHOULD BE LOCATED ON THE SAME | | SIDE OF THE SECURITY FENCE. IF THE | | PRESENT SECURITY FENCE IS NOT MODIFIED | | THEN THESE DEVICES SHOULD BE LOCATED | | OUTSIDE OF IT. | | 2) COULD NOT LOCATE CODE SECTION 5-12 | | REGARDING SINGLE EXIT AND TRAVEL | | DISTANCE OF 100 FEET. PLEASE PROVIDE | | APPLICABLE CODE SECTION. | | 3) EIGHTEEN FEET MUST BE PROVIDED FROM | | FIRE HYDRANTS TO ANY OBSTRUCTIONS PER | | CITY CODE REQUIREMENTS. | | 4) PLEASE PROVIDE MORE DETAILS ON | | EMERGENCY GENERATOR. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|