2001-04-24 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
  
 1.SIGN SHALL BE POSTED ON MACHINERY
 ROOM DOOR PROHIBITING ACCESS OF
 UNAUTHORIZED PERSONNEL.
  
 2.EXHAUST OUTLETS SHALL BE LOCATED
 10 FT FROM ANY DOOR, WINDOW OR AIR
 INTAKE AND AT LEAST 10 FT ABOVE THE
 ADJOINING GRADE LEVEL. 1997 SMC
 506.1 - (H1.1B).
  
 3.AS PER 1997 SMC 1105.8, AT LEAST
 ONE APPROVED SELF-CONTAINED
 BREATHING APPARATUS, SUITABLE
 FOR THE REGRIGERANT USED, SHALL BE
 AVAILABLE TO AUTHORIZED PERSONNEL
 AT A LOCATION CONVENIENT TO THE
 MACHINERY ROOM.
  
 4.DRAWING E2.1B INDICATES ONE
 REFRIGERANT LEAK DETECTOR WILL THIS
 SUFFICE FOR THREE CHILLERS?ALSO,
 IS THIS TIED INTO THE AUDIBLE/
 VISUAL ALARM?
  
 5.ARE THERE TO BE ANY ALARMS LOCATED
 OUTSIDE THE DOORS OF THE CHILLER
 ROOM IN CASE OF A REFRIGERANT LEAK.
  
 6.DRAWING H1.2B, (3) 2" CHILLER
 REFIEF RISERS TERMINATE 15' ABOVE
 ROOF, SHALL ALSO BE NOT LESS THAN
 20' FROM ANY VENTILATION OPENING IN
 REFERENCE TO INTAKE LOUVER TO THE
 CHILLED WATER PUMP ROOM.
  
 7.PLEASE PROVIDE LOCATION OF THE
 BOILERS AND ALSO PROVIDE DETAILS
 OF PIPING AND VENTILAITON FOR
 THE BOILER ROOM.