Date |
Text |
2001-04-12 00:00:00 | 1) BOLLARDS SHOWN ON PAGE C1 ARE NOT |
| TO INTERFERE WITH OPERATION OF THE |
| FIRE HYDRANT. |
| 2) ANY ROOM CONTAINING FLAMMABLE OR |
| COMBUSTIBLE LIQUIDS MUST BE SEPARATED |
| FROM OTHER PARTS BY AT LEAST A TWO |
| HOUR FIRE SEPARATION. OPENINGS ARE TO |
| BE PROTECTED BY B LABELED (1 1/2 HOUR) |
| FIRE DOORS WITH CLOSERS. ADEQUATE |
| VETILATION IS TO BE PROVIDED. |
| 3) STAIRS TO COMPLY WITH NEW STAIRS |
| PER NFPA 101, THE LIFE SAFETY CODE, |
| 1985 EDITION. |
| 4) HANDRAILS AND GUARDS TO COMPLY WITH |
| NFPA 101, THE LIFE SAFETY CODE, 1985 |
| EDITION. |
| 5) THE FIRE DEPARTMENT CONNECTION SHOWN |
| ON PAGE FP1.1B IS TO BE WITHIN 150 FEET |
| OF A FIRE HYDRANT. THE REMOVAL AND |
| RE-INSTALLATION OF THE FIRE PUMP SHALL |
| BE GIVEN THE HIGHEST PRIORITY FOR |
| COMPLETION. |
| 6) EMERGENCY LIGHTING REQUIRED IN FIRE |
| PUMP ROOM. |
| 7) PLEASE EXPLAIN RATIONALE FOR EXITING |
| FROM THE SECOND FLOOR. EXIT STAIR # 6 |
| IS LOCATED IN A STORAGE ROOM AND |
| TERMINATES IN A STORAGE ROOM. |
| 8) PROVIDE MORE DETAILS ON EMERGENCY |
| GENERATOR AND APPURTENANT EQUIPMENT. |
| 9) PLEASE INDICATE REFRIGERANT PLANNED |
| FOR USE. PLEASE INDICATE EMERGENCY |
| WARNING EQUIPMENT, SIGNS, AND SELF |
| CONTAINED BREATHING APPARATUS USED IN |
| THE EVENT OF A REFRIGERANT LEAK. |
| 10) SEPARATE PLANS AND PERMITS REQUIRED |
| FOR THE FIRE ALARM REMODEL. CUT SHEETS, |
| WIRING DIAGRAM, AND BATTERY CALCULATIONS |
| ARE REQUIRED. |
| |