Plan Review Notes
Plan Review Notes For Permit 01040393
Permit Number 01040393
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-04-12 00:00:00FAILED:
 1. INSUFFICIENT INFORMATION FOR CIVIL
 ENGINEERING REVIEW.PLEASE RESUBMIT
 WHEN CIVIL PLANS ARE DEVELOPED.
 2. PLEASE PROVIDE DRAINAGE CALCULATIONS
 & PLANS TO JOSE DEL RIO, STORM WATER
 ENGINEER, 100045TH STREEET WEST PALM
 BEACH, FL 33415(561) 659-8040
 3. PLEASE PROVIDE PERVIOUS & IMPERVIOUS
 CALCULATION FOR ENTIRE SITE DUE TO
 PROPOSED CHANGES, SIGNED & SEALED BY
 DESIGN ENGINEER.PLEASE SUBMIT THIS
 INFORMATION ON A 8 1/2 X 11 SHEET TO
 MANNY GONZALEZ, PROJECT COORDINATE
 SPECIALIST, 100045TH STREET WEST PALM
 BEACH, FL 33415 (561) 659-8040
 4. PERMIT FROM HEALTH DEPARTMENT MUST BE
 OBTAINED FOR RELOCATING THE FIRE HYDRANT
 IF THE DISTANCE FORM MAIN IS MORE THAN
 50'.
 5. PLEASE STATE IF GARBAGE IS TO BE
 PICKED UP BY THE CITY OR PRIVATE PICK UP
 ,IF TO BE PICKED UP BY THE CITY, THEN AN
 APPROVAL FROM PUBLIC UTILITIES
 DEPARTMENT, JOHNNY THOMAS, SOLID WASTE
 SUPERINTENDENT IS REQUIRED.THE OPENING
 BETWEEN THE GATE POSTS MAY NOT BE
 ADEQUTE FOR DOUBLE DUMPSTERS AS SHOWN.
 IF ANY QUESTION PLEASE CONTACT 561- 659-
 8096 EXT. 8492