Plan Review Notes For Permit 01040393 |
Permit Number |
01040393 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-04-19 00:00:00 | ****************** UNSAT ************* | | | | 1)NOTE: PLEASE SHOW ALL LOAD | | CALCULATIONS, TO INCLUDE AMPERAGES. | | PLEASE NOTE THAT ALL CONTINUOUS AND | | LARGEST MOTOR LOADS NEED TO BE SHOWN AT | | 125%. ALL PER | | 215-5, 215-2, 215-3. | | | | 2)NOTE: PLEASE NOTE FOR GROUPING OF | | MEANS OF DISCONNECT FOR POWER COMING | | FROM | | GENERATOR PER 230-72, 230-76,230-79. | | | | 3)NOTE: PLEASE NOTE THAT UNDER PALM | | BEACH COUNTYWIDE AND CITY OF WEST PALM | | BEACHAMENDMENTS: COLOR CODING IN SPEC | | BOOK FOR 277/480V IS SHOWN B,O,Y. THIS | | NEEDS TO BE BROWN, PURPLE YELLOW. | | ART;215 LOCAL.AMENDMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANYQUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|