2001-04-19 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE SHOW ALL LOAD
 CALCULATIONS, TO INCLUDE AMPERAGES.
 PLEASE NOTE THAT ALL CONTINUOUS AND
 LARGEST MOTOR LOADS NEED TO BE SHOWN AT
 125%. ALL PER
 215-5, 215-2, 215-3.
  
 2)NOTE: PLEASE NOTE FOR GROUPING OF
 MEANS OF DISCONNECT FOR POWER COMING
 FROM
 GENERATOR PER 230-72, 230-76,230-79.
  
 3)NOTE: PLEASE NOTE THAT UNDER PALM
 BEACH COUNTYWIDE AND CITY OF WEST PALM
 BEACHAMENDMENTS: COLOR CODING IN SPEC
 BOOK FOR 277/480V IS SHOWN B,O,Y. THIS
 NEEDS TO BE BROWN, PURPLE YELLOW.
 ART;215 LOCAL.AMENDMENTS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS,
 PLEASE CALL.
  