Plan Review Notes For Permit 01040095 |
Permit Number |
01040095 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-10-23 00:00:00 | ******************** UNSAT ************ | | | | 1)NOTE: PLEASE NOTE THAT PLANS WERE | | SUBMITTED AND ARE FOR "FINAL" "CO". | | PLEASE NOTE THAT THE CODE ART REFERENCED | | FOR GROUNDING ELECTRODE CONDUCTORS, | | ARE UNDER "96 NEC. ART FOR "99" NEC IS | | 250-50. | | COLD WATER PIPE ALSO,,,(IF METAL) | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMNET | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | PANEL. PER 250-122 | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW | | BEFORE FINAL.IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|