Plan Review Notes For Permit 01031119 |
Permit Number |
01031119 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-04-02 00:00:00 | *******************DENIED*************** | | | | AS PER 1997 SMC 406.2, FAN SHUTDOWN BY | | DUCT SMOKE DETECTOR IS REQUIRED FOR ANY | | UNIT SERVING AN AREA USED FOR MEANS OF | | EGRESS AND SHALL HAVE NOTIFICATION TO | | TO ALARM/STROBE. SHOW COMPLIANCE WITH | | NFPA 90A 4-4.4.2 OR 4-4.4.3. | | | | CONDERSER WATER PIPING DONE IN COPPER | | SHALL BE BRAZED AS PER 1997 SMC 1206.1 |
|