Plan Review Notes For Permit 01031119
Permit Number 01031119
Review Stop M
Sequence Number 1
Notes
Date Text
2001-04-02 00:00:00*******************DENIED***************
  
 AS PER 1997 SMC 406.2, FAN SHUTDOWN BY
 DUCT SMOKE DETECTOR IS REQUIRED FOR ANY
 UNIT SERVING AN AREA USED FOR MEANS OF
 EGRESS AND SHALL HAVE NOTIFICATION TO
 TO ALARM/STROBE. SHOW COMPLIANCE WITH
 NFPA 90A 4-4.4.2 OR 4-4.4.3.
  
 CONDERSER WATER PIPING DONE IN COPPER
 SHALL BE BRAZED AS PER 1997 SMC 1206.1